8 ABB Power Distribution
2.3 Dimensions and weights
Rated voltage kV 12 17.5
Height
2)
Dimension a mm 2200 2200
Width Dimension b
• Tee-off current up to 1250 A (up to 31.5 kA) mm 650 650
• Tee-off current up to 1250 A (above 31.5 kA) mm 800 800
• Tee-off current 1600 A mm 800/1000 800/1000
• Tee-off current above 1600 A mm 1000 1000
Depth Dimension c mm 1300
1)
1300
1)
1)
1350 mm for rated tee-off currents of 4000 A
2)
Height of the control cabinet is 705 mm
AV
a
bc
The minimum ceiling height in the switchroom is 3000 mm. Further details of the switchroom design can be found
in figures 5/1 to 5/4.
Weights:
Feeder panel (including withdrawable circuit-breaker part)
Weight
kg
Rated current Rated short-time current
A …31,5 kA …50 kA
…1250 800 850
1600 850 850
2000 1200 1200
2500 1200 1200
3150 1200 1200
4000 1400 1400