EasyManua.ls Logo

Ablerex TAURUS 10 kVA - Page 48

Ablerex TAURUS 10 kVA
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.4.2 Cold Start
(1) User can start-up UPS by battery when main input power is not available.
(2) Select CommandOperationCold start precharge ready on LCD display.
(3) Select Normal mode to start UPS.
3.4.3 Shutdown
(1) Select CommandOperationShutdown on LCD display.
3.4.4 Switch to bypass
(1) Select CommandOperationShutdownconverter except bypass on LCD
display.
(2) The Inverter will be shutdown and bypass will supply the power to the load. If the
battery is disconnected, Rectifier and Charger will be shutdown as well.
3.4.5 Switch from normal mode to maintenance bypass
(1) Select CommandOperationShutdown converter except bypass on
LCD display.
(2) The Inverter will be shutdown and bypass will supply the power to the load
(3) Open the Main Input and Battery Switches
(4) Close the maintenance bypass switch
(5) Open Output and Bypass switch
(6) Wait at least for 10min
3.4.6 Maintenance bypass → normal mode
(1) Close Output, Mains Input and Bypassswitches
(2) Select CommandOperationShutdown converter except bypasson LCD
display.
(3) Open maintenance bypass switch
(4) Select CommandOperationNormal mode on LCD display.
(5) Return to Mimic Display. Wait for few minutes, the rectifier will be start and the
icon will show you when can close the Batteryline switch/fuses to connect
the batteries.
46
192321262008007

Related product manuals