www.accuenergy.com
V: 1.0 Revised: Jan. 2018
81
Appendix
Address
(Hex)
Address
(dec)
Parameter Range Default Data Type Property
0112H 274 AO2 Upper Limit 0 ~ 100(%) 100 Word R/W
0113H 275 RO1 Mode
0: Latch; 1: Momentary;
2: Alarm
2 Word R/W
0114H 276
RO1 Momentary
Time Delay
300~5000ms 1000 Word R/W
0115H 277
RO1 Alarm Pa-
rameter
0: No Alarm; 1: Voltage; 2:
Current; 3: Power
0 Word R/W
0116H 278
RO1 Alarm In-
equality
0: Smaller than;
1: Larger than
0 Word R/W
0117H 279
RO1 Alarm Time
Delay
0~255 S 5 Word R/W
280-281
RO1 Alarm
Threshold
The same as full range
values
Float
011AH 282 RO2 Mode
0: Latch; 1: Momentary;
2: Alarm
2 Word R/W
011BH 283
RO2 Momentary
Time Delay
300~5000ms 1000 Word R/W
011CH 284
RO2 Alarm Pa-
rameter
0: No Alarm; 1: Voltage; 2:
Current; 3: Power
0 Word R/W
011DH 285
RO2 Alarm In-
equality
0: Smaller than;
1: Larger than
0 Word R/W
011EH 286
RO2 Alarm Time
Delay
0~255 S 5 Word R/W
011FH-
0120H
287-288
RO2 Alarm
Threshold
The same as full range
values
Float R/W
0121H 289
Backlight Bright-
ness Level
1~5 5 Word R/W
0122H 290 Clear Energy 0X0A: Enable Word W
0123H 291
Clear Meter Run-
ning Hour
0X0A: Enable Word W
0124H 292
Clear Load Run-
ning Hour
0X0A: Enable Word W
0125H 293 DI Working Mode
according to Bit value:
0: Level mode;
1: Count mode;
Bit0: DI1 working mode;
Bit1: DI2 working mode
3 Word R/W
0126H 294
Clear DI Count
Value
according to Bit value:
0: Not clear;
1: Clear
Bit0: Clear DI1
Bit1: Clear DI2
Word W
0127H 295 Clear Ah 0X0A: Effective Word W
0128H 296
Clear MAX/MIN
Value
0X0A: Effective Word W
0129H 297
Clear Data Log-
ging
0X0A: Effective Word W