ACOWA INSTRUMENTS, Industrivej 10, 8305 Samsø - VAT-no: 36562919 – mail: info@acowa.dk – Phone: +45 7221 7979
Pumpword: Register 70
Status
Warning
Alarm
Bit 16: Pump - Manual mode by SCADA
√
Bit 17: Pump - started manually by SCADA (Requires bit 16 = 1)
√
Bit 18: Stop - manual mode
√
PUMA status: Register 92
Status
Warning
Alarm
Bit 0: “Running blind” control active
√
Bit 1: Internal
√
Bit 2: Internal power supply failure
√
Bit 3: Internal
Bit 4: Pump in error plus high level
√
Bit 5: Internal
Bit 6: External power supply failure
√
Bit 7: Transmitter error
√
Bit 8: Pump in operation
√
Bit 9: Internal
Bit 10: Internal
Bit 11: Control in alarm
√
Bit 12: Warning leakage
√
Bit 13: Pump capacity needs update
√
Bit 14: Internal
Bit 15: Internal
Bit 16: Internal
Bit 17: Internal
Bit 18: Internal
Bit 19: Internal
Bit 20: Back-stop control
√
Bit 21: Internal
Bit 22: Internal
Bit 23: Internal
Bit 24: Internal
Bit 25: Waiting for depth pumping
√
Bit 26: High level switch
√