Specifications
6\VWHP 2YHUYLHZ
Unimode 400 Installation PN 50710:A 10/22/97 1-5
1RWLILFDWLRQ$SSOLDQFHDQG5HOHDVLQJ&LUFXLWV
036,&0,&(
Table 1-5 contains specifications for NACs and releasing circuits available on the
MPS-400:
Table 1-5 NACs and Releasing Circuits
5HOD\V
Relays for Alarm, Trouble, Security, and Supervisory are available on MPS-400
terminals TB3 to TB6. Contact ratings for TB3-TB6 are:
• 2.0 A @ 30 VDC (resistive);
• 0.5 A 30 VAC (resistive) when used for a Form-C relay.
)RXUZLUH6PRNH'HWHFWRU3RZHU
1RWH
7KH 036 SURYLGHV D
WRWDO RI $ RI SRZHU VKDUHG
E\ DOO LQWHUQDO PRGXOHV DQG
HDFK 036 FLUFXLW )RU
SRZHU UHTXLUHPHQWV UHIHU WR
WKH SRZHU VXSSO\ FDOFXODWLRQ
WDEOHV LQ $SSHQGL[ *
MPS-400 terminals TB2-5 (+) and TB2-6 (–) supply filtered, resettable, low-noise
power for four-wire smoke detectors. Specifications for TB2-5 and TB2-6 are:
• Maximum ripple voltage: 10 mVrms
• Up to 1.25 A is available for powering four-wire smoke detectors.
For 24 VDC detectors, refer to the Device Compatibility Document for compatible
detectors.
Item Value
Maximum wiring voltage drop 2 VDC (except M500CH which is 1.2 VDC)
Normal operating voltage 24 VDC
Current for all external devices
connected to MPS-400
6.0 A (except devices powered from the AVPS-24 or
AA-30 and AA-120, or FCPS-24)
Optional AVPS-24 Additional 3.0 A of NAC power for each AVPS-24
(requires ICM-4 modules)
Maximum signaling current/
circuit (MPS-400)
2.5 A (except M500CH which is 2 A)
End-of-line resistors MPS-400 (TB-7–TB-10): 2.2K, 1/2 watt
ICM-4, ICE-4, VCM-4, CE-4, and DCM-4: 4.7K,
1/2 watt (2 watts on 70 Vrms audio)