End-of-Line Devices
 6\VWHP 2YHUYLHZ
Unimode 400 Installation PN 50710:A 10/22/97 1-13
(QGRI/LQH'HYLFHV
Table 1-10 contains a list of the end-of-line devices that you can install in a
Unimode 400 system:
Table 1-10 End-of-Line Devices
Option Description Notes
A2143-00
(System Sensor)
A 47K End-Of-Line Resistor
(ELR) Assembly ELR used in the
supervision of M500M or
M501M Monitor and M500CH
Control Module circuits.
Supplied with M500M or
M500CH modules.
A2143-10
(System Sensor)
The 3.9K End-Of-Line Resistor
(ELR) Assembly used with the
M502M.
Supplied with M502M
modules.
N-ELR Resistor plate
(Notifier)
An N-ELR, required for
Canadian installations, provides
connection for a resistor to mount
to an ELR plate.
Use 2.2K for the
MPS-400 output.
Use 4.7K for ICM-4,
ICE-4, VCM-4, VCE-4,
and DCM-4.
Use 47K for M500CH,
M500M, and M501M
modules.