Preparing for Installation
,QVWDOODWLRQ
Unimode 400 Installation PN 50710:A 10/22/97 2-1
,QVWDOODWLRQ
3UHSDULQJIRU,QVWDOODWLRQ
8QSDFNLQJ WKH 6\VWHP
Unpack the system as follows:
%HIRUH LQVWDOOLQJ WKH ILUH DODUP V\VWHP UHDG WKH IROORZLQJ
Install the system in a readily accessible area with sufficient room to easily install
and maintain the control panel.
Locate the top of the cabinet approximately 60 inches above the floor with the
hinge mounting on the left.
Count the number of conductors needed for all devices and find the appropriate
knockouts.
Review the installation precautions at the front of this manual.
All wiring must comply with the National and/or Local codes for fire alarm
systems.
Do not draw wiring into the bottom 9 inches of the cabinet, except when using the
BB-17 or BB-55 battery box. This prevents interference between the power supply
and batteries.
6WDQGDUGV DQG &RGHV
In addition, installers should be familiar with the following
standards:
NEC Article 300 Wiring Methods.
NEC Article 760 Fire Protective Signaling Systems.
Applicable Local and State Building Codes.
Requirements of the Local Authority Having Jurisdiction.
Step Action
1 Carefully unpack the system and inspect for shipping damage.
2 Select a location for the control panel in a clean, dry, vibration-free area with
moderate temperature.