EasyManua.ls Logo

Advantage Controls MegaTron - Boiler Conductivity and Auxiliary Inputs; Boiler Conductivity Sampling Methods; Auxiliary Input Configuration

Advantage Controls MegaTron
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
2.4 Boiler Conductivity
Conductivity on boiler systems can be congured for Timed Sampling, Sample and Hold or Continuous for
the conductivity sampling method.
Timed sampling incorporates a sample timer which allows the boiler to be sampled at periodic intervals.
Sample intervals are adjustable from 1 minute to 99 hours, 59 min. Sample duration (on-time) is adjustable
from 1 second to 99 minutes, 59 seconds.
Sample and hold uses a sample timer for periodic sampling intervals. The unit will sample for its duration
then hold the blowdown valve closed for a settable period (hold time). The conductivity is checked at the end
of the hold period, if additional blowdown is required the blowdown valve is held open for a preset amount of
time (blowdown time). Then sample cycle is repeated.
Continuous sample has a sample of boiler or condensate water go past the probe continuously. If the
reading is above the set point, blowdown will continue until the set point has been satised.
SET POINT - What reading turns the relay on
DIFFERENTIAL - Amount reading changes by before
the relay is turned o󰀨
HIGH ALARM - What reading generates a High alarm
notication.
LOW ALARM - What reading generates a Low alarm
notication.
SAMPLE INT - Period between samples.
SAMPLE DUR - How long a sample lasts.
HOLD TIME - How long a hold lasts.
BLOWDOWN - How long to blowdown if reading is
above the set point after the hold. Hold repeated after
BLOWDOWN time.
2.5 Aux Inputs
Auxiliary inputs are the digital inputs for optional Flow Switch and other digital inputs such as low drum level
alarms. From these menus the user can set if they want each of the alarms Displayed, Remote Notication,
both or none.
>SYSTEM 1 COND SETPOINT<
SET POINT SAMPLE INT
DIFFERENTIAL SAMPLE DUR
HIGH ALARM HOLD TIME
LOW ALARM BLOWDOWN
>SYSTEM 1 DIGITAL INPUTS ALARM<
ALARM NOTIFICATION DIGITAL 1
FLOW SW = DISPLAY DIGITAL 2
DIGITAL 1 = DISPLAY DIGITAL 3
DIGITAL 4
FLOW ALARM DIGITAL 5

Other manuals for Advantage Controls MegaTron

Related product manuals