4-66 ADAM 4000 Series User's Manual
$AA1Ci
Name Single Channel Offset Calibration
Description The command calibrates a specified channel to correct for offset
errors.
Syntax $AA1Ci(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module which is to be calibrated.
1 represents the offset calibration command.
Ci represent the specified input channel you want to calibrate.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! delimiter character indicates a valid command was received.
? delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
(cr) represents terminating character, carriage return (0Dh).
Example command: $021C5(cr)
response: !02(cr)
The command calibrates channel 5 of the analog input module
at address 02 for correcting offset errors.
4015, 4019

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM-4017 and is the answer not in the manual?

Advantech ADAM-4017 Specifications

General IconGeneral
BrandAdvantech
ModelADAM-4017
CategoryControl Unit
LanguageEnglish

Related product manuals