Chapter 4 Command Set 4-115
Chapter 4
Name Read Low Alarm Limit
Description The addressed module is asked to return its Low alarm limit
value.
Syntax @AARL(cr)
@
is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
RL
is the Read Low Alarm Limit command.
(cr)
represents terminating character, carriage return (0Dh).
Response !AA(data)(cr)
if the command was valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
!
delimiter character indicating a valid command was received.
AA
represents the 2-character hexadecimal address of the
responding analog input module.
(data) is the value of the Low alarm limit in engineering units.
(cr)
represents terminating character,
carriage return (0Dh).
Example command: @05RL(cr)
response: !05-0.3750(cr)
Presume the analog input module at address 05h is configured
to accept 1 V input. The command instructs the module to
return it Low alarm limit value.
The module responds its Low alarm limit value is -0.3750 V.
4011, 4011D, 4012, 4014D, 4016