4-122 ADAM 4000 Series User's Manual
Command Set
4016
$AAS
Name Start-up Voltage Output Configuration
Description Stores the present analog output value of the strain gauge input
module with address AA in the modules non-volatile register.
The output value will take effect upon start-up or after a
brownout.
Syntax $AAS(cr)
$ is a delimiter character.
AA(range 00-FF) represents the 2-character hexadecimal
address of the strain gauge input module whose analog output
is to be set.
S is the start-up voltage output configuration command.
(cr) is the terminating character, carriage return (0Dh)
Response !AA(cr) if the command is valid.
?AA(cr) if an invalid command was issued.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the strain gauge input module.
(cr) is the terminating character, carriage return (0Dh)
NOTICE: A strain gauge input module requires a maximum of 6 millisec-
onds after it received a Startup Voltage Output Configuration command to
let the settings take effect. During this interval, the module can not be
addressed to perform any other actions.