Chapter 4 Command Set 4-209
Chapter 4
4080
@AADO
Name Set Digital Output
Description Set the values of the modules two digital outputs (ON or OFF).
Syntax @AADO(data)(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
DO is the Set Digital Output command
(data) is the two-character parameter that sets the state for the
two digital output bits of the module, as shown below:
00 all D/O bits are OFF
01 bit 0 is ON, bit 1 is OFF
02 bit 0 is OFF, bit 1 is ON
03 all bits are ON
(cr) represents terminating character, carriage return (0Dh)
Response !AA(cr) if the command was valid
?AA(cr) if an invalid parameter was entered
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! delimiter character indicating a valid command was received
? delimiter character indicating the command was invalid
AA represents the 2-character hexadecimal address of the
responding counter module.
(cr) represents terminating character, carriage return (0Dh)
Example command: @05DO01(cr)
response: !05(cr)
The counter module at address 05h is instructed to set digital
output channel 1 to ON and digital output channel 2 to OFF.
The module confirms the settings.
4080, 4080D

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM-4017 and is the answer not in the manual?

Advantech ADAM-4017 Specifications

General IconGeneral
BrandAdvantech
ModelADAM-4017
CategoryControl Unit
LanguageEnglish

Related product manuals