4-214 ADAM 4000 Series User's Manual
4080
Command Set
@AACA
Name Clear Latch Alarm
Description Both alarm states (High and Low) of the addressed counter
module are set to OFF, no alarm.
Syntax @AACA(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of an counter module.
CA is the Clear Latch Alarm command
(cr) represents terminating character, carriage return (0Dh)
Response !AA(cr) if the command was valid
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! is a delimiter character indicating a valid command was valid
AA represents the 2-character hexadecimal address of the
responding counter module.
(cr) represents terminating character, carriage return (0Dh)
Example command: @05CA(cr)
response: !05(cr)
The counter module at address 05h is instructed to set
both alarm states (High and Low) to OFF. The module confirms
that it has done so.