4-216 ADAM 4000 Series User's Manual
4080
Command Set
@AASA(data)
Name Set Hi-alarm Count Value of Counter 0.
Description Set the high-alarm count value for counter 0 of the specified
counter module.
Syntax @AASA(data)(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address a the counter module.
SA identifies the Set High-alarm Count Value command.
(data) is the high-alarm count value which must consist of eight
hexadecimal digits. This value should be higher than the low-
alarm count value.
(cr) is the terminating character, carriage return (0Dh)
Response !AA(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! is a delimiter character indicating a valid command
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
(cr) is the terminating character, carriage return (0Dh).
Example command: @12SAF0000000(cr)
response: !12(cr)
The command sets the low-alarm count number F0000000(hex)
for channel 0 of the counter modules at address 12. The
addressed module replies that the command has been received.
4080D