EasyManuals Logo

Advantech ADAM-4017 User Manual

Advantech ADAM-4017
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #302 background imageLoading...
Page #302 background image
4-218 ADAM 4000 Series User's Manual
4080
Command Set
@AARA
Name Read High-alarm Count Value for Counter 0.
Description Requests the addressed counter module to return its high-alarm
count value of counter 0.
Syntax @AARA(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
RA identifies the Read High-alarm Count Value command
(cr) is the terminating character, carriage return (0Dh)
Response !AA(data)(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! a delimiter character indicating a valid command
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
(data) is the high-alarm count value which consists of eight
hexadecimal digits.
(cr) is the terminating character, carriage return (0Dh).
Example command: @12RA(cr)
response: !12F0000000(cr)
The command instructs the module at address 12 to return its
high-alarm count value. The module replies that counter 0's
high-alarm count value is F0000000(hex).
4080D

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM-4017 and is the answer not in the manual?

Advantech ADAM-4017 Specifications

General IconGeneral
BrandAdvantech
ModelADAM-4017
CategoryControl Unit
LanguageEnglish

Related product manuals