ADAM-6300 User Manual 10
3.1 Specifications
3.1.1 General
Power input: 10 ~ 30 V
DC
LAN: 10/100Base-T(X)
Connectors: 2 x RJ-45 (LAN), 1 MAC ID; Plug-in screw terminal block (I/O and
power)
Screw terminal block: Accepts wire size #16-28 AWG, stripped length: 6.5 mm
Watchdog: System and Communication
Real-time clock accuracy: 2 seconds per day
Certification: CE, FCC
3.1.2 Protection
Power Reversal Protection
3.1.3 Environment
Operating temperature: -25 ~ 70 °C (-13 ~ 158 °F)
Storage temperature: -40 ~ 85 °C (-40 ~ 185 °F)
Operating humidity: 20 ~ 95% RH (non-condensing)
Storage humidity: 0 ~ 95% RH (non-condensing)
3.1.4 OPC UA Specification
Supports Address Space, Session, Monitored item, and Subscription
Security Policy
An endpoint security policy is a predefined communication mode that mandates a
combination of security algorithms and optionally message signing and encryption.
Endpoint Security Policy: None
Endpoint Security Policy: Sign - Basic128Rsa15
Authentication Policy
User Token Anonymous - Token Security Policy None
User Token Username / Password - Token Security Policy Basic128Rsa15
Supports 8 certificates
Items Max Remark
Max Monitored Items 600 Including all sessions
Max Sessions 4
The maximum sessions supported, includ-
ing security and non security session.
Max Subscriptions per Session 1
Note! ADAM-6300 supports 4 session including security and non security ses-
sions. User can disconnect sessions in Utility and remove sessions they
don't need.
Note! ADAM-6300 supports 8 certificates. Click Delete Certificates and
ADAM-6300 will be automatically restart and then remove certificates
that are not needed.