UPS OPERATING INSTRUCTIONS
PROTECT 1.100
PROTECT 1.150
PROTECT 1.200
PROTECT 1.

Table of Contents

Questions and Answers

  • G
    Gregory MartinAug 15, 2025
    What to do if the 'Fault' LED lights up and the warning signal sounds twice per second on my AEG PROTECT 1.100?
    • J
      Jordan MathisAug 16, 2025
      If the 'Fault' LED is illuminated and the warning signal sounds twice per second, this indicates an overload of the AEG UPS system. To resolve this, immediately reduce the capacity utilization of the UPS by disconnecting some of your loads.
  • M
    Mary DunnAug 18, 2025
    Why are the 'Line' and 'Fault' LEDs lit with a continuous warning signal on my AEG PROTECT 1.100 UPS?
    • J
      James JohnsonAug 18, 2025
      The simultaneous illumination of the 'Line' and 'Fault' LEDs accompanied by a continuous warning signal indicates a switch-off due to the AEG UPS's internal overtemperature detection. Ensure that there is no overload, the UPS fans are not blocked, and the ambient temperature is within the correct range. Allow the UPS to cool down for 10 minutes before switching it back on.
  • A
    ashley63Aug 21, 2025
    What to do if the AEG PROTECT 1.100 UPS switches to battery mode?
    • K
      kellypatelAug 21, 2025
      The AEG UPS switches to battery mode because the mains voltage supply has been interrupted. Try to re-establish the mains voltage, checking for triggered fuses. If the acoustic signal sounds every second, the battery is almost completely discharged. Immediately perform a system shutdown of your IT equipment.
  • M
    moraleskatherineAug 25, 2025
    How to troubleshoot no display and no acoustic signal on my AEG PROTECT 1.100?
    • K
      Kristen CooperAug 25, 2025
      If there is no display and no acoustic signal, even when the system is connected to the mains, the mains and/or battery voltage may be outside the tolerance range, or the battery may be totally discharged. Check the mains connection, the back-up fuse, and the mains input miniature circuit breaker.
  • P
    Patrick SmithAug 28, 2025
    Why is the emergency power supply duration shorter than expected on my AEG UPS?
    • J
      Julie HolmesAug 28, 2025
      The emergency power supply duration might be shorter than the setpoint because the batteries are not completely charged or they are aged or faulty. Charge the batteries for at least the recharging time. If the problem persists, contact your dealer.
  • J
    Jenna HendersonAug 30, 2025
    What does it mean when the 'Line' LED flashes and the 'Battery' LED lights up on my AEG PROTECT 1.100 UPS?
    • J
      Jacob JohnsonAug 30, 2025
      When the 'Line' LED flashes and the 'Battery' LED is lit, the mains voltage and/or mains frequency are outside of tolerance. Check the mains voltage and frequency.
  • J
    Jean KeithSep 3, 2025
    What to do if my AEG UPS does not switch to bypass even when mains is OK?
    • L
      linda03Sep 3, 2025
      If the AEG UPS does not switch to bypass even when the mains is OK, the mains input use may be in the “OFF” position. Switch the mains input miniature circuit breaker to “ON”.
  • R
    Robin DavenportSep 5, 2025
    How to fix error description no. 19 on my AEG PROTECT 1.100 UPS?
    • J
      jonathan45Sep 5, 2025
      Error description no. 19 indicates a switch-off due to a short-circuit in the AEG UPS output. Correct the short-circuit, then switch the UPS on again, connecting loads one after the other.
  • T
    timothy79Sep 8, 2025
    What does it mean if the 'Fault' LED lights up, the 'Battery' LED flashes, and a warning signal sounds once per second on my AEG PROTECT 1.100 UPS?
    • L
      Leslie DavisSep 8, 2025
      If the 'Fault' LED lights up, the 'Battery' LED flashes, and the warning signal sounds once per second, this indicates a fault in the DC circuit or a faulty battery system. Notify your dealer.
  • J
    Joshua ChavezSep 12, 2025
    What does it mean when the 'Fault' LED lights up with a continuous warning signal on my AEG UPS?
    • M
      Michael SchmidtSep 12, 2025
      If the 'Fault' LED is illuminated with a continuous warning signal, this indicates a fault in the AEG UPS. Notify your dealer.

Summary

General Information

Technical Data

Lists detailed technical specifications for UPS input, output, and type ratings.

Safety Regulations

Important Instructions and Explanations

Emphasizes compliance with safety regulations for personnel and unit availability.

Accident Prevention Regulations

Mandates compliance with country-specific accident prevention and IEC 364 safety regulations.

Qualified Personnel

Defines qualified personnel for transport, installation, and servicing of the PROTECT 1. UPS.

General Safety Instructions

Covers crucial safety warnings, handling, environment, electric shocks, and battery precautions.

Set-up Procedures

Unpacking and Inspection

Guides on checking the unit for damage and verifying the completeness of the delivery.

Display

Explains the function of each LED and pushbutton on the UPS display panel.

Rear view (connections)

Illustrates the rear view and connection terminals for PROTECT 1.100 and 1.150/1.200.

Electrical Connection

Cable and Fuse Specifications

Checklist for cable connections and details on cross-sections and fuse protection.

Start-Up and Operating Modes

Unit overload

Warns about exceeding rated load, its consequences, and avoiding household appliances connection.

Interfaces and Communication

Displays and Troubleshooting

Overview Table of LED Displays; Acoustic Warning Signals

Provides a table summarizing LED displays and acoustic signals for various operating modes and faults.

Faults

Details fault management and provides a guide to identifying and resolving UPS malfunctions.

Error Messages

Lists common error messages, their causes, and suggested solutions for troubleshooting.

Parallel Operation

Operation of the UPS in a parallel system

Describes the procedures for operating and managing UPS units in a parallel configuration.

Start-Up

Details the start-up procedure for a parallel UPS system, including bypass and isolator settings.

Maintenance

AEG PROTECT 1.100 Specifications

General IconGeneral
Apparent power1000 VA
Real power600 W
Nominal input voltage230 V
Output voltage230 V
Output frequency50/60 Hz
Output voltage regulation± 10%
TopologyLine Interactive
Waveform typeSinewave
Communication portsUSB
Efficiency95%
Operating Temperature0 - 40 °C
Storage Temperature-15 - 45 °C
Humidity0 - 95% non-condensing
Typical backup time at full load5 minutes
Battery TypeSealed Lead Acid
Battery Recharge Time4-6 hours
Protection FeaturesOverload, short circuit