CONTROL PANEL OPERATING PROCEDURES
3-7
Table 3-4. Configuration Menu - Continued
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
4 – 20 mA/1
5V
0 -20 mA/0
5V
PWM Input
(BMS)
Network
4 – 20
mA,
1-5V
Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F
230°F
70°F
Reset Ratio
(If Mode = Outdoor
Reset)
0.1
9.9
1.2
Outdoor Sensor Enabled or Disabled Disabled
System Start Tmp
(If Outdoor Sensor =
Enabled)
30°F
100°F
60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit Setpt Lo Limit 195°F 195°F
Temp Hi Limit
40°F
210°F
195F
Max Fire Rate
40%
100%
100%
Pump Delay Timer 0 min. 30 min. 0 min.
Aux Start On Dly 0 sec. 120 sec. 0 sec.
Failsafe Mode Shutdown or Constant Setpt Shutdown
*Analog Output
(See CAUTION at
end of Table 3-4 )
Off, Setpoint, Outlet
Temp,
Valve Position 4-20
mA,
Valve Position
0-10V
*Valve
Position
0-10V
Low Fire Timer 2 sec. 600 sec. 2 sec.
Setpt Limiting Enabled or Disabled Disabled
Setpt Limit Band
0°F
10°F
5°F
Network Timeout 5
Sec
999 Sec 30 Sec
HI DB Setpt EN
0%
100%
30%
Demand Offsert
0
25
10
Deadband High
0
25
2
Deadband Low
0
25
2
*CAUTION:
1. DO NOT CHANGE the Analog Output Menu Item from its Default setting (Valve
Position 0-10V).