How to resolve an Airflow Fault during Run on my Aerco Benchmark BMK 750?
- LLawrence SmithNov 27, 2025
If the Aerco Boiler experiences an Airflow Fault during Run, several factors could be at play. The blower might have stopped running due to thermal or current overload; check the combustion blower for signs of excessive heat or high current draw. A blocked blower inlet or inlet ductwork is another possibility; inspect the inlet to the combustion blower, including any ductwork leading up to it, for signs of blockage. A blockage in the air filter or Blocked Inlet switch could also be the cause; remove the air filter and Blocked Inlet switch and inspect for signs of blockage, cleaning or replacing as necessary. A defective Blocked Inlet switch may also be the problem; verify that 24 VAC is present between each side of the switch and ground. If 24 VAC is not present at both sides, replace swit...