EasyManua.ls Logo

Aerco BENCHMARK 6000 - User Manual

Aerco BENCHMARK 6000
210 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
OMM-0086_0D AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 1 of 210
GF-133 Ph.: 800-526-0288 03/20/14
BENCHMARK 6000
Gas-Fired Boiler
USER MANUAL
Installation, Operation and Maintenance
Natural Gas Modulating &
Condensing Hot Water Boiler
Applicable to Serial Numbers:
N-14-0172 and Above
Latest Update: 03/20/14

Table of Contents

Questions and Answers

  • C
    Charles RobinsonSep 18, 2025
    Why is the exhaust temperature high in my Aerco Boiler?
    • J
      Jeff SchroederSep 18, 2025
      If the Aerco Boiler displays a High Exhaust Temperature, the combustion calibration may be off. Check the combustion calibration using procedures in Chapter 4. If the exhaust temperature exceeds 200°F, it may be caused by a carboned heat exchanger due to incorrect combustion calibration. Calibrate or repair as necessary.
  • M
    Michael JohnsonAug 25, 2025
    What to do if Aerco BENCHMARK 6000 experiences flame loss during run?
    • L
      laura57Aug 26, 2025
      If the Aerco Boiler experiences flame loss during operation, several factors could be responsible. First, inspect the flame detector for wear or cracks in the ceramic and replace if needed. Second, check the gas pressure into and out of the air/fuel valve using a gauge or manometer to ensure it's correct, as a defective regulator can cause this issue. Third, ensure proper combustion calibration; if it's off, recalibrate following the procedures in Chapter 4. Fourth, remove the burner and check for carbon build-up or debris, cleaning and reinstalling it if necessary. Fifth, clear any blockages in the condensate drain. Finally, make sure the main flame detector isn't touching the burner mesh; if it is, straighten or replace it.
  • V
    Victoria OlsenAug 27, 2025
    What to do if Aerco BENCHMARK 6000 displays Airflow Fault during Run?
    • A
      Amber RamirezAug 27, 2025
      If the Aerco Boiler is showing an Airflow Fault during Run, start by checking the combustion blower for signs of excessive heat or current draw that may be tripping thermal or current overload devices. Next, inspect the inlet to the combustion blower, including any ductwork leading up to it, for blockages. Then, remove the air filter and Blocked Inlet switch to inspect for blockages; clean or replace as needed. Finally, verify that 24 VAC is present between each side of the Blocked Inlet switch and ground; replace the switch if 24 VAC is not present at both sides.
  • M
    michaelvazquezDec 1, 2025
    What causes flame loss during ignition on Aerco BENCHMARK 6000 Boiler?
    • M
      Michelle CoxDec 1, 2025
      If your Aerco Boiler is experiencing flame loss during ignition, consider these steps: * Inspect the flame detector for wear and replace if necessary. * Close the internal gas valve in the unit. Install and arc a spark igniter outside the unit to check for a spark. * If there's no spark, check for 120VAC at the primary side of the ignition transformer during the ignition cycle. * If 120VAC is not present, the IGST Board in the Control Box may be defective. Refer fault to qualified service personnel. * While externally arcing the spark igniter, observe the open/close indicator in the SSOV to ensure it's opening. If the valve doesn't open, check for 120VAC at the valve input terminals. If 120VAC is not present, the IGST board in the Control Box may be defective. Refer fault to qua...
  • S
    Samuel LucasSep 22, 2025
    How to resolve Direct Drive Signal Fault on Aerco BENCHMARK 6000 Boiler?
    • K
      Kimberly EllisonSep 22, 2025
      If the Aerco Boiler is showing a Direct Drive Signal Fault, check the I/O Box to ensure the signal is hooked up; hook it up if it's not installed. If it is installed, check the polarity and measure the signal level. Also, check the wiring continuity between the source and the unit. Check the signal at the source to ensure it is isolated. Check the DIP switch on the PMC board to ensure it is set correctly for the type of signal being sent. Check the control signal type set in the Configuration Menu.
  • R
    Randy BradleyNov 27, 2025
    How to troubleshoot airflow fault during ignition in Aerco Boiler?
    • B
      brandoncunninghamNov 27, 2025
      To troubleshoot an airflow fault during ignition in your Aerco Boiler, consider these potential causes: * The blower might have stopped due to thermal or current overload. Inspect the combustion blower for signs of excessive heat or high current drain. * There could be a blockage in the blower inlet or inlet air filter. Inspect the inlet to the combustion blower, including the air filter at the air/fuel valve, for any obstructions. * The blower proof switch might be blocked. Remove the blower proof switch and inspect for blockages, cleaning or replacing it as needed. * A blocked inlet switch might be obstructed. Remove the blocked inlet switch and inspect for blockages; clean or replace if necessary. * The blower proof switch could be defective. Check its continuity with the com...
  • J
    Janet ScottSep 12, 2025
    What causes remote setpt signal fault in Aerco Boiler?
    • N
      Natalie BridgesSep 12, 2025
      If your Aerco Boiler is showing a 'Remote Setpt Signal Fault', here's what you should check: * Ensure the remote setpoint signal is present by checking the I/O Box to ensure the signal is connected. Connect it if it's not installed. If it is installed, check the polarity and measure the signal level. Also, check the continuity of wiring between the source and the unit. * If using a 4 to 20 mA signal, verify that the signal is isolated at the source. * Check the DIP switch on the PMC board to ensure it's correctly set for the type of signal being sent (voltage or current). Also, check the control signal type set in the Configuration menu.
  • K
    keithperezSep 12, 2025
    What causes recirculation pump failure in Aerco Boiler?
    • P
      Peggy WeberSep 12, 2025
      If your Aerco Boiler is experiencing a recirculation pump failure, it indicates that the internal recirculation pump has failed and needs to be replaced.
  • J
    Jordan JamesDec 1, 2025
    What to do if Aerco Boiler shows airflow fault during purge?
    • M
      mary70Dec 1, 2025
      If your Aerco Boiler experiences an airflow fault during purge, here's what you can check: * The blower might not be running or is running too slowly. Start the unit and check the blower solid-state relay for input and output voltage. If the relay is okay, inspect the blower itself. * The blocked inlet switch could be defective. Start the unit, and if the blower runs, turn off the unit and check the blocked inlet switch for continuity. Replace the switch if continuity does not exist. * There may be a blockage in the air filter or blocked inlet switch. Remove the air filter and blocked inlet switch and inspect for any obstructions. Clean or replace as needed. * The blower inlet or inlet ductwork might be blocked. Inspect the inlet to the combustion blower, including any ductwork le...
  • G
    Gina WrightSep 5, 2025
    What causes line voltage out of phase error in Aerco BENCHMARK 6000?
    • P
      Paul WintersSep 5, 2025
      If your Aerco Boiler displays a 'Line Voltage Out of Phase' error, check the following: * Ensure the hot and neutral wires are not switched in the AC Power Box. * Verify the transformer wiring in the AC Power Box against the power box transformer wiring diagram to ensure it's wired correctly.

Summary

CHAPTER 1. SAFETY PRECAUTIONS

1.1 WARNINGS & CAUTIONS

General safety regulations, warnings, and cautions for installers and operating personnel.

1.2 EMERGENCY SHUTDOWN

Procedure for emergency shutdown of the boiler in case of overheating or gas supply failure.

CHAPTER 2. INSTALLATION

2.9 AC ELECTRICAL POWER WIRING

Guidance on connecting AC power wiring to the unit, referencing GF-2060.

2.9.1 Electrical Power Requirements

Details on available voltage configurations and power box terminal blocks.

2.10 FIELD CONTROL WIRING

Information on factory-wired internal control systems and external control features.

CHAPTER 3. OPERATION

3.2 CONTROL PANEL DESCRIPTION

Description of the C-More Control Panel, its controls, indicators, and displays.

3.3 CONTROL PANEL MENUS

Overview of the menu structure for setting up and configuring the unit.

3.6 CONFIGURATION MENU

Menu for adjusting internal setpoint and other configuration settings.

3.8 COMBUSTION CAL MENU

Menu for performing combustion calibration to optimize efficiency and emissions.

3.9 BST (BOILER SEQUENCING TECHNOLOGY ) MENU

Menu for configuring, operating, and monitoring the Boiler Sequencing Technology system.

3.10 START SEQUENCE

Checks pre-purge safety switches and initiates the start sequence.

CHAPTER 4. INITIAL START-UP

4.1 INITIAL START-UP REQUIREMENTS

Requirements for initial boiler start-up, including installation, controls, calibration, and testing.

4.2 TOOLS AND INSTRUMENTATION FOR COMBUSTION CALIBRATION

Necessary tools and instrumentation for performing combustion calibration.

4.2.1 Required Tools & Instrumentation

List of tools and instrumentation needed for combustion calibration.

4.3 PILOT IGNITION

Description of the pilot ignition system and its components.

4.4 NATURAL GAS COMBUSTION CALIBRATION

Procedures for calibrating combustion for low and ultra-low NOx emissions.

CHAPTER 5. MODE OF OPERATION

5.2 INDOOR;OUTDOOR RESET MODE

Mode based on outside air temperature to adjust supply header temperature.

5.3 CONSTANT SETPOINT MODE

Mode used for fixed header temperature applications like heat pump loops.

5.4 REMOTE SETPOINT MODES

Mode allowing remote control of setpoint via EMS or BAS using current or voltage signals.

5.5 DIRECT DRIVE MODES

Mode where air/fuel valve position is controlled by a remote signal.

5.6 AERCO CONTROL SYSTEM (ACS)

Mode for operating multiple boilers efficiently using an AERCO Control System.

5.7 COMBINATION CONTROL SYSTEM (CCS)

System using multiple boilers for space heating and domestic hot water needs.

CHAPTER 6. SAFETY DEVICE TESTING

6.1 TESTING OF SAFETY DEVICES

Importance of periodic safety device testing to ensure proper operation and compliance.

6.2 LOW GAS PRESSURE FAULT TESTS

Procedures for testing the low gas pressure fault switch.

6.3 HIGH GAS PRESSURE FAULT TEST

Procedures for simulating and testing the high gas pressure fault.

6.4 LOW WATER LEVEL FAULT TEST

Procedure to simulate and test the low water level fault condition.

6.5 WATER TEMPERATURE FAULT TEST

Procedure to simulate and test the high water temperature fault.

6.6 INTERLOCK TESTS

Tests for the Remote Interlock and Delayed Interlock circuits.

6.6.1 Remote Interlock Test

Procedure for testing the Remote Interlock circuit.

6.6.2 Delayed Interlock Test

Procedure for testing the Delayed Interlock circuit.

6.7 FLAME FAULT TESTS

Procedures to simulate and test flame fault conditions.

6.8 AIR FLOW FAULT TESTS

Tests for the Blower Proof Switch and Blocked Inlet Switch.

6.8.1 Blower Proof Switch Test

Procedure for testing the Blower Proof Switch.

6.8.2 Blocked Inlet Switch Test

Procedure for testing the Blocked Inlet Switch.

6.9 SSOV PROOF OF CLOSURE SWITCH

Checking the proof of closure (POC) switch circuit for the downstream SSOV.

6.10 PURGE SWITCH OPEN DURING PURGE

Checking the purge switch located on the Air/Fuel Valve.

6.11 IGNITION SWITCH OPEN DURING IGNITION

Checking the ignition switch located on the Air/Fuel Valve.

6.12 SAFETY PRESSURE RELIEF VALVE TEST

Testing the safety pressure relief valve per ASME code.

CHAPTER 7. MAINTENANCE

7.1 MAINTENANCE SCHEDULE

Routine maintenance schedule for efficiency and reliability.

7.2 PILOT BURNER

Location and maintenance procedure for the pilot burner.

7.3 MAIN FLAME DETECTOR

Location and maintenance procedure for the main flame detector.

7.5 COMBUSTION CALIBRATION & PILOT REGULATOR ADJUSTMENT

Checking combustion settings and performing pilot regulator adjustments.

7.6 SAFETY DEVICE TESTING

Systematic testing of operating and safety devices.

CHAPTER 8. TROUBLESHOOTING GUIDE

8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES

Troubleshooting faults that do not display specific error messages.

CHAPTER 9 - RS-232 COMMUNICATION

CHAPTER 10. BOILER SEQUENCING TECHNOLOGY

APPENDIX A - BOILER MENU ITEM DESCRIPTIONS

COMBUSTION CAL MENU

Descriptions of menu items for the Combustion Calibration Menu.

APPENDIX J: RECOMMENDED PERIODIC TESTING

APPENDIX N - ULTRA-LOW NOX CALIBRATION

N-1. ULTRA-LOW NOx COMBUSTION CALIBRATION

Procedures to calibrate the boiler for ultra-low NOx emissions.

Aerco BENCHMARK 6000 Specifications

General IconGeneral
ModelBENCHMARK 6000
TypeCondensing Boiler
Input BTU/hr6, 000, 000 BTU/hr
Fuel TypeNatural Gas or Propane
Heat ExchangerStainless Steel
Operating Pressure160 psi
Input Capacity6, 000, 000 BTU/hr
Vent Diameter6"

Related product manuals