Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
APPENDIX A BOILER MENU DESCRIPTIONS
OMM-0086_0D AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 155 of 210
GF-133 Ph.: 800-526-0288 03/20/14
APPENDIX A: BOILER MENU ITEM DESCRIPTIONS Continued
TUNING MENU DESCRIPTION
COMBUSTION CAL MENU
NOTE: The Level 2 Password must be entered to view the options in the Combustion Cal
Menu. This Menu is used during the Combustion Calibration procedures described in
Chapter 4 of this Manual.
CAL Voltage 14%
CAL Voltage 30%
CAL Voltage 40%
CAL Voltage 50%
CAL Voltage 70%
CAL Voltage 100%
Displays the default DC drive voltage provided to the
blower at each of the Air/Fuel Valve positions show in
the left-hand column. This drive voltage adjusts the
rotational speed of the blower to maximize
combustion efficiency.
Set Valve Position Permits selection of the Air/Fuel Valve position (%
open) to be set from 0 to 100%.
Blower Output Permits the DC drive voltage to the blower to be
monitored.
Set Stby V out Permits the Standby Voltage to be set from 0 to 4.00
Volts.
Oxygen Level Permits the combustion oxygen level to be displayed
(0% to 25%).