Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0078_0L AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 45 of 206
GF-128 Phone: 800-526-0288 PRI: 11/25/2014
Table 3-4. Configuration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1 Internal Setpt Lo Temp Limit Hi Temp Limit 130°F
2 Unit Type Innovation WH Innovation WH
3 Unit Size
600 MBH, 800 MBH, 1060 MBH,
1350 MBH
600, 800, 1060 or
1350 MBH
4 Fuel Type Natural Gas, Propane Natural Gas
5
Water Heater Mode
Constant Setpoint,
Remote Setpoint,
Constant Setpoint
6
Remote Signal
(If Mode = Remote Setpoint,
Direct Drive or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (Legacy BMS),
Network
4 – 20 mA,
1-5V
7 Outdoor Sensor Enabled or Disabled Disabled
8
System Start Tmp
(If Outdoor Sensor =Enabled)
30°F 100°F 60°F
9
Setpt Lo Limit 40°F Setpt Hi Limit 60°F
10
Setpt Hi Limit Setpt Lo Limit 190°F 150°F
11 Temp Hi Limit 40°F 200°F 160°F
12
Max Valve Position 40% 100% 100%
13
Pump Delay Timer 0 min. 30 min. 0 min.
14 Aux Start On Dly 0 sec. 120 sec. 0 sec.
15
Failsafe Mode Shutdown or Constant Setpt Shutdown
16
* Analog Output
Off, Setpoint, Outlet Temp, Valve Pos
4-20mA, valve Pos 0-10v
Valve Pos 0-10v
17 Low Fire Timer 2 sec. 600 sec. 2 sec.
18
Setpt Limiting Enabled or Disabled Disabled
19
Setpt Limit Band 0°F 10°F 0
20 Network Timeout 5 Sec 999 Sec 30 Sec
21
Shutoff Dly Temp 0 25 8
22
Demand Offset 0 25 5
23
Deadband High 0 25 0
24
Deadband Low 0 25 0