EasyManuals Logo

Aerco KC Series User Manual

Aerco KC Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
CONTROL PANEL OPERATING PROCEDURES
3-7
Table 3-4. Configuration Menu - Continued
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Low Fire Timer 2 sec. 600 sec. 2 sec.
Setpt Limiting Enabled or Disabled Disabled
Setpt Limit Band 0°F 10°F 5°F
Network Timeout 5 Sec 999 Sec 30 Sec
HI DB Setpt EN 0% 100% 30%
Demand Offsert 0 25 10
Deadband High 0 25 2
Deadband Low 0 25 2
*CAUTION:
DO NOT CHANGE the Analog Output Menu Item from its Default setting
(Valve Position 0-10V).
3.7. TUNING MENU
The Tuning Menu items in Table 3-5 are Factory
set for each individual unit.
Do not change these menu entries unless
specifically requested to do so by factory trained
personnel.
Table 3-5. Tuning Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Min Load Adj
-50°F
50°F
0°F
Max Load Adj
-50°F
50°F
0°F
FFWD Temp
30°F
245°F
Outlet Feedback
On
Off
On
Reset Defaults?
Yes
No
Are You Sure?
No

Other manuals for Aerco KC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aerco KC Series and is the answer not in the manual?

Aerco KC Series Specifications

General IconGeneral
BrandAerco
ModelKC Series
CategoryWater Heater
LanguageEnglish

Related product manuals