WATER HEATER DEFAULT SETTINGS - Continued
MENU & OPTION FACTORY DEFAULT
Tuning Menu
Prop Band 8°F
Integral Gain 1.60
Derivative Time 0.10 min
Min Load Adj 0°F
Max Load Adj 0°F
FFWD Temp N/A
Outlet Feedback On
Feedback Gain 0.05
Breakpoint At 100% 77°F
Breakpoint At 90% 81°F
Breakpoint At 80% 85°F
Breakpoint At 70% 91°F
Breakpoint At 60% 95°F
Breakpoint At 50% 102°F
Breakpoint At 40% 110°F
Breakpoint At 30% 112°F
Breakpoint At 20% 114°F
Breakpoint At 10% 130°F
Breakpoint At 0% 135°F