EasyManua.ls Logo

AERMEC DI24 - Page 25

AERMEC DI24
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
QR- code
Scan the following QR- code for the APP operating manual:
CONTROL VIA AERSUITE
The AerSuite application allows remote control of the DI24 user interface, with VMF-E19/VMF-E19I thermostats, via Smart Devices with iOS and Android
operating systems. It is an application for Smartphones and Tablets with which the user will be able to remotely access and manage the operation of their
system. For more information on the use of the application and available functions, please refer to the respective documentation in the Qr-code shown.
Parameter index Parameter name Range of values Description
P6
FS2 33 - 66 % Fan speed in V2 mode
P7
FS3 66 - 100 % Fan speed in V3 mode
P8
AIR PROBE 0 - 2
0. Local Using the air probe in the user
interface
1. Thermostat Using the air probe in the
fancoil on-board thermostat
2. Average use the average value given by the
ara probes present
P9
AUX 0 - 1
0. Disabled AUX mode cannot be selected
1. Enabled AUX mode can be selected
P10
FLP 0 - 101 %
Value of the ap position in the GLF_M/GLFI_M
grids, if FLP = 101 the louvers swing function is
enabled.
P11
ATA -5.0 - 5.0 C
Parameter for air reading correction via
probe in panel
P12
CFU 0 - 1
Temperature unit selection:
0. °C
°C
1. °F
°F
P13
TFO 0 - 1
0. Static display
Disabled
1. Dynamic display
Enabled
P14
TSP 0 - 1
Set point display mode if an external
supervisor is present:
0. Absolute
Actual setpoint
1. Dierential
Deviation
P15
WIFI 0 - 2
0. Wi OFF
Wi module o
1. Wi ON
Wi module on in client mode
2. Hotspot
Wi module on in host mode
(only when conguring the App)
EN

Related product manuals