EasyManua.ls Logo

AERMEC FK360 - FK Air Conditioner Commissioning and Checks; Operating Test Procedure; Post-Installation Checks

AERMEC FK360
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
Aermec. 16.01. 5140901_01
9. OPERATING TEST
Preparing for the test
Check that the network voltage is correct.
Do not connect the unit to the power supply before installation is
complete.
Ensure that the connection and supply cables are correctly
connected to the unit.
Ensure that the gas and liquid pipe valves are open.
Remove any dust and swarf created during installation.
Running the test
Give voltage to the unit, press the ON/OFF button (by remote
control) to start the test.
Repeatedly press the MODE button, select COOL, DRY, FAN, etc. and
check that operation is normal.
Check the operation of the condensate discharge.
Before commissioning the air conditioner, an operating test must be performed. Proceed as follows:
10. ROUTINE CHECKS FOLLOWING INSTALLATION
ITEMS TO CHECK POSSIBLE ANOMALY SITUATION
Is the unit firmly fixed? The unit could fall, vibrate or generate noise.
Has a check for refrigerant leaks been
performed?
Poor performance.
Is the thermal insulation sufficient? It could cause condensate and dripping water.
Does the unit correctly drain the condensate
water?
It could cause condensate and dripping water.
Does the power supply voltage correspond to
the one indicated on the label?
Electrical operating fault or damage to
components which could be blown.
Have the cables and pipes been connected
correctly and safely?
Electrical operating fault or damage to
components which could be blown.
Has the unit been safely grounded via an earth
connection?
Risk of electrocution. Damage to components.
Have the guidelines the manual regarding
electric cable type and section been followed?
Failure to do so could cause electrical
operating faults or damage to components
which could be blown.
Are the air inlet and outlet on the indoor unit
free of obstacles?
Poor performance.
Have the pipe length and refrigerant charge
been recorded?
Poor performance. Impossible to check the
amount of refrigerant added.

Related product manuals