FUNZIONAMENTO
OPERATION
TAB. A
Impostazione visualizzata Descrizione
Min. Default Max.
Accesso
Setting visualised Description Access
SET-FREDDO temperatura acqua ingresso evaporatore
-6 °C 11 °C 20 °C
Libero
COLD SET
evaporator water inlet temperature Free
SET-CALDO temperatura ingresso condensatore (solo su pompa calore)
30 °C 45 °C 55 °C
Libero
HOT SET
condenser inlet temperature (heat pump only) Free
DIF. GRAD. differenziale gradino
0,5 °C 1 °C 3 °C
Libero
STEP DIFF
capacity step differential Free
DIF. TOT. differenziale totale
1 °C 2 °C 6 °C
Libero
TOT. DIFF
total differential Free
SET-AGC1 temperatura antigelo circuito 1
-9 °C 3 °C 4 °C
Con codice
C1 AF SET
antifreeze temperature circuit 1 With code
SET-AGC2 temperatura antigelo circuito 2
-9 °C 3 °C 4 °C
Con codice
C2 AF SET
antifreeze temperature circuit 2 With code
ESC. BP tempo di esclusione intervento pressostato di bassa
180 s 180 s 360 s
Con codice
LP SHUTOFF
low pressure switch delay With code
P. IN. S. pressione di inizio sbrinamento
1,5 bar 3 bar 5 bar
Con codice
D START
defrost start pressure With code
T. OUT. S. temperatura liquido fine sbrinamento
10 °C 20 °C 30 °C
Con codice
D STOP
defrost end liquid temperature With code
Codice segreto impostazione nuovo codice segreto
Con codice
Access code
new password setting With code
ORE CP1 azzeramento ore funzionamento compressore 1
Con codice
CP1 TIME
cancel working hours compressor 1 With code
ORE CP2 azzeramento ore funzionamento compressore 2
Con codice
CP2 TIME
cancel working hours compressor 2 With code
Lingua selezione lingua Italiano, Inglese, Tedesco, Francese (0-1-2-3)
0 0 3
Con codice
Language
language select Italian, English, German, French (0-1-2-3) With code
Autostart inserimento partenza automatica per mancanza di tensione
Auto
Con codice
Autostart
set automatic start after power cut With code
TAB. A
Sigla Descrizione Mod.
Code Description
SAE temperatura aria esterna •
ambient air temperature
NRA - NRC - NRS - RS
SIR temperatura acqua ingresso recuperatore •
recuperator inlet water temperature
NSW
SIW temperatura acqua ingresso evaporatore •
evaporator water inlet temperature
NRA - NRC - NRS - RS - NBW - NSW
SIWH temperatura acqua ingresso condensatore •
condenser water inlet temperature
solo •
only
NBW H - NSW H
SL1 temperatura freon liquido circuito 1 •
refrigerant liquid temperature circuit 1
NRA - NRC - NRS - RS
SL2 temperatura freon liquido circuito 2 •
refrigerant liquid temperature circuit 2
NRA - NRC - NRS - RS
SUR1 temp. acqua uscita recuperatore circuito 1 •
recuperator circuit 1 outlet water temp.
NSW
SUR2 temp. acqua uscita recuperatore circuito 2 •
recuperator circuit 2 outlet water temp.
NSW
SUW temperatura uscita acqua •
outlet water temperature
NRS - RS
SUW1 temperatura uscita acqua circuito 1 •
outlet water temperature circuit 1
NRA - NRC - NBW - NSW
SUW2 temperatura uscita acqua circuito 2 •
outlet water temperature circuit 2
NRA - NRC - NBW - NSW
SUWH1 temp. acqua uscita condensatore circ. 1 •
condenser water outlet temp. circ. 1
solo •
only
NBW H - NSW H
SUWH2 temp. acqua uscita condensatore circ. 2 •
condenser water outlet temp. circ. 2
solo •
only
NBW H - NSW H
TAP1 pressione di mandata circuito 1 •
delivery pressure circuit 1
NRA - NRC - NRS - RS - NBW - NSW
TAP2 pressione di mandata circuito 2 •
delivery pressure circuit 2
NRA - NRC - NRS - RS - NBW - NSW
TBP1 pressione d’aspirazione circuito 1 •
suction pressure circuit 1
NRA - NRC - NRS - RS - NBW - NSW
TBP2 pressione d’aspirazione circuito 2 •
suction pressure circuit 2
NRA - NRC - NRS - RS - NBW - NSW