21.05 – 5167557_02 7
- Install the unit at a distance enough from the exhaust wells, to ensure
that the possible loss of gas may reach and pollute the aquifer
- Keep all lubricants in properly marked containers do not keep
ammable liquids near the plant
- Do not remove the protections from mobile elements while the unit
is running
- Do not use cables with inadequate section or ying connections, not
even for limited periods or emergencies
- Check the unit is properly earthed before starting it
- Before opening the electrical panel, disconnect the unit from the
mains by means of the external isolator
- In case of units with shunt capacitors, wait 3 minutes from when
power supply was disconnected from the unit before accessing inside
the electrical panel
- If the unit is equipped with integrated inverter compressors,
disconnect the power supply and wait at least 15 minutes before
accessing for maintenance: the internal components remain live for
this time, generating the risk of electrocution
- The safety devices must be maintained ecient and periodically
checked as prescribed by current regulations
- In case a piece is disassembled, make sure it is correctly reassembled
before restarting the unit
- Even with the unit o, prevent the uid in contact with the
heat exchangers exceed the temperature limits indicated in the
documentation and freeze.
- Do not send the heat exchangers uids other than water or its
mixtures with ethylene glycol/propylene in a maximum concentration
of 30%
- The machine must only be employed for the use for which it was
made; any other use can be dangerous and void the warranty
PREVENTIONS
- Make sure that the protections of mobile elements are correctly in
place before restarting the unit
- Fans, motors and belt drives may be in motion: always wait for them
to stop and take appropriate precautions to prevent their activation
before accessing them
- The machine and the pipes have very hot and very cold surfaces that
lead to risk of burns
- Before opening a machine panel, ascertain whether it is or not rmly
connected to it by hinges
- Louvers of the heat exchangers, edges of the components and metal
panels can generate cuts
- The installation must ensure that the temperature of the uid
entering the unit is maintained stable and within the provided limits;
therefore, pay attention to the adjustment of any external thermal
exchange and control devices (drycooler, evaporating towers,
area valves, ...), to the adequate dimensioning of the mass of uid
circulating in the plant (in particular when plant areas are excluded)
and to install systems for the recirculation of the necessary uid ow
rate so as to maintain the machine temperatures within the allowed
limits (e.g. during the start-up phase).
- The material used for the machine protective packaging must always
be kept out of the reach of children as it is a source of danger
- In units with compressors in parallel, do not disable the individual
compressors for long periods.
- This is an appliance not accessible to the general public.