5. STARTING CURRENT REDUCTION IN PRESENCE OF DRE ACCESSORIES
MODEL SINGLE CIRCUIT DOUBLE CIRCUIT THREE-CIRCUIT FOUR-CIRCUIT FIVE-CIRCUIT SIX-CIRCUIT
CURRENT REDUCTION
-30% -26% -22% -20% -18% -16%
13
INRLPY. 02.10 4086916_01
6. TECHNICAL DATA
6.1. TECHNICAL DATA VERSIONS [°-L]
COOLING 2800 3000 3300 3600
Cooling output kW
°
676 750 824 898
L 604 672 733 786
Total input power kW
°
284 322 350 374
L 314 354 384 416
Water flow rate l/h
°
116270 129000 141730 154460
L 103890 115580 125900 135190
Total pressure drops kPa
°
73.0 78.6 59.5 58.8
L 59.1 63.8 47.9 45.9
Energy indices
EER W/W
°
2.38 2.33 2.35 2.40
L 1.92 1.90 1.90 1.89
ESEER W/W
° 3.76 3.68 3.72 3.79
L 3.65 3.61 3.62 3.59
ELECTRICAL DATA
Fuel feed A
°
400V - 3 - 50 Hz
L
Input current A
°
498 572 610 638
L 538 616 656 696
Maximum current A
°
580 638 716 782
L
Peak current A
°
789 847 984 1050
L
COMPRESSORS (SCROLL)
Number/Circuit
no./
no.
°
10/4 12/4 12/4 12/4
L
FANS (AXIAL)
Quantity no.
°
8 8 12 12
L
Air ow rate m³/h
°
154000 152000 216600 212400
L 115400 121600 151620 148680
Input power kW
° 10.0 10.0 15.0 15.0
L 7.5 7.5 11.3 11.3
Input current A
°
21.6 21.6 32.4 32.4
L 16.2 16.2 24.3 24.3
Useful heads
[1]
Pa
°
45 45 40 40
L----
FANS (ENLARGED M)
Quantity no.
°
8 8 12 12
L
Input power kW
°
13.9 13.9 20.9 20.9
L ----
Input current A
° 29.6 29.6 44.4 44.4
L ----
Useful heads
[1]
Pa
° 45 45 40 40
L----