17
INRLPY. 02.10 4086916_01
(1) Sound power
Aermec determines the sound power value on the basis of measurements
taken in accordance with standard 9614-2, in compliance with the Eurovent
certifi cation.
(2) Sound pressure
Sound pressure in an unrestricted range on a refl ective plane (directional
fact. Q=2), 10m away from the unit external surface, complying with ISO 3744.
8. TECHNICAL DATA
8.1. TECHNICAL DATA VERSIONS [C]
COOLING 2800 3000 3300 3600
Cooling capacity: kW
°
704 782 860 938
L 630 702 766 820
Total input power kW
°
294 332 364 388
L 326 366 398 432
Energy indices
EER W/W
°
2.39 2.36 2.36 2.42
L 1.93 1.92 1.92 1.90
ELECTRICAL DATA
Fuel feed A
°
400V - 3 - 50 Hz
L
Input current A
°
516 594 632 662
L 558 638 680 722
Maximum current A
°
580 638 716 782
L
Peak current A
°
789 847 984 1050
L
COMPRESSORS (SCROLL)
Number/Circuit
no./
no.
°
10/4 12/4 12/4 12/4
L
1/4
FANS (AXIAL)
Quantity no.
°
8 8 12 12
L
Air fl ow rate m³/h
°
154000 152000 216600 212400
L 115400 121600 151620 148680
Input power kW
°
10.0 10.0 15.0 15.0
L 7.5 7.5 11.3 11.3
Input current A
°
22 22 32 32
L 16 16 24 24
SOUND DATA
Sound power (1) dBA
° 93.5 93.5 95 95
L 90.5 90.5 92 92
Sound pressure (2) dBA
° 61.5 61.5 63 63
L 58.5 58.5 60.0 60.0
DIMENSIONS
Height mm
H
2450 2450 2450 2450
HL
Width mm
H
2200 2200 2200 2200
HL
Depth mm
H
8100 8100 8100 8100
HL