EasyManua.ls Logo

AERMEC NRL - 8. TECHNICAL DATA; 8.1. TECHNICAL DATA VERSIONS [C]

AERMEC NRL
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
INRLPY. 02.10 4086916_01
(1) Sound power
Aermec determines the sound power value on the basis of measurements
taken in accordance with standard 9614-2, in compliance with the Eurovent
certi cation.
(2) Sound pressure
Sound pressure in an unrestricted range on a re ective plane (directional
fact. Q=2), 10m away from the unit external surface, complying with ISO 3744.
8. TECHNICAL DATA
8.1. TECHNICAL DATA VERSIONS [C]
COOLING 2800 3000 3300 3600
Cooling capacity: kW
°
704 782 860 938
L 630 702 766 820
Total input power kW
°
294 332 364 388
L 326 366 398 432
Energy indices
EER W/W
°
2.39 2.36 2.36 2.42
L 1.93 1.92 1.92 1.90
ELECTRICAL DATA
Fuel feed A
°
400V - 3 - 50 Hz
L
Input current A
°
516 594 632 662
L 558 638 680 722
Maximum current A
°
580 638 716 782
L
Peak current A
°
789 847 984 1050
L
COMPRESSORS (SCROLL)
Number/Circuit
no./
no.
°
10/4 12/4 12/4 12/4
L
1/4
FANS (AXIAL)
Quantity no.
°
8 8 12 12
L
Air ow rate m³/h
°
154000 152000 216600 212400
L 115400 121600 151620 148680
Input power kW
°
10.0 10.0 15.0 15.0
L 7.5 7.5 11.3 11.3
Input current A
°
22 22 32 32
L 16 16 24 24
SOUND DATA
Sound power (1) dBA
° 93.5 93.5 95 95
L 90.5 90.5 92 92
Sound pressure (2) dBA
° 61.5 61.5 63 63
L 58.5 58.5 60.0 60.0
DIMENSIONS
Height mm
H
2450 2450 2450 2450
HL
Width mm
H
2200 2200 2200 2200
HL
Depth mm
H
8100 8100 8100 8100
HL

Table of Contents

Related product manuals