AERMEC NXP 0650 - Electric Cable; Electrical Data Version °; L Without Pumping Group

AERMEC NXP 0650
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
L1 L2 L3
PHASE
EARTH (PE)
Power Supply:
Size
NXP
Power supply Compressors
TOTAL INPUT
Recommended cable cross section
Power cables
Control and
safeties
connection
Earth
IL
F.L.A. L.R.A. Phases
Cables per
phases
Cross section Total cables Cross section Cross section
(n°) (A) (A) (n°) (n°) (mm
2
) (n°) (mm
2
) (mm
2
) (A)
0500 400V/3/50Hz 3 71.4
214.5 3 1 16 3 1,5 16 100
0550 400V/3/50Hz 3 76.6 219.7 3 1 16 3 1,5 16 100
0600 400V/3/50Hz 4 91.3 163.7 3 1 25 3 1,5 16 125
0650 400V/3/50Hz 4 101.7 190.9 3 1 25 3 1,5 16 125
0700 400V/3/50Hz 4 123.7 235.8 3 1 35 3 1,5 16 160
0750 400V/3/50Hz 4 134.7 286.8 3 1 50 3 1,5 25 160
0800 400V/3/50Hz 4 162.9 291.5 3 1 70 3 1,5 35 200
0900 400V/3/50Hz 4 178.9 299.5 3 1 70 3 1,5 35 200
1000 400V/3/50Hz 4 194.9 307.4 3 1 70 3 1,5 35 250
1250 400V/3/50Hz 4 207.8 375.9 3 1 95 3 1,5 50 250
1400 400V/3/50Hz 4 237.1 428.6 3 1 95 3 1,5 50 250
1500 400V/3/50Hz 4 266.1 443.1 3 1 120 3 1,5 70 320
1650 400V/3/50Hz 4 295.1 555.6 3 1 120 3 1,5 70 320
F.L.A. Maximum current from unit
L.R.A. Peak current from unit
Earth Earth wire to connect to unit
IL Master switch
ELECTRICAL DATA VERSION ° / L WITHOUT PUMPING GROUP