20
HYDRAULIC CONNECTIONS



ATTENTION The choice and installaon of components external to the unit
is up to the installer, who must operate according to the rules of good
technical design and in compliance with the regulaons in force in the
country of desnaon.
ATTENTION The hydraulic connecon pipes to the unit must be suitably
dimensioned for the effecve water flow rate requested by the system
when running. The water flow rate to the heat exchanger must always be
constant
ATTENTION Wash the system thoroughly before connecng the unit. This
cleaning will eliminate any residues such as welding drips, scale, rust, or
other impuries from the piping. These substances can also deposit inside
and cause unit malfuncons. The connecon piping must be adequately
supported so that its weight does not rest on the appliance










 


 


 

 
 

 
 

 



 
ATTENTION You must install the water filter supplied, in the hydraulic
circuit upstream of the heat exchanger. FAILURE TO DO THIS INVALIDATES
THE WARRANTY.
ATTENTION The charge or discharge of the heat exchange fluids must
be made during installaon by qualified technicians using the fings
provided on the hydraulic circuit. Never use the unit heat exchangers to
top-up the heat exchanger fluid.




 
 


 


ATTENTION: the addion of glycol is the only effecve protecon against
freezing; the glycol/water soluon must be sufficiently concentrated
to ensure proper protecon and prevent ice forming at minimum
temperature provided for a given installaon. Take the necessary
precauons if using non-passivated an-freeze soluons (monoethylene
glycol or monopropylene glycol). Corrosion phenomena may occur with
these an-freeze soluons in contact with oxygen.
However, always refer to the glycol supplier documentaon to check its
recommended concentraon.
WATER FEATURES
System: Chiller with plate heat exchanger
PH 7,5-9
Electric conductivity 100-500S/cm
Total hardness 4,5-8,5°dH
Temperature < 65°C
Oxygen content < 0,1 ppm
Max. glycol amount 50%
Phosphates (PO4) < 2ppm
Manganese (Mn) < 0,05 ppm
Iron (Fe) < 0,3 ppm
Alkalinity (HCO3) 70 - 300 ppm
Chloride ions (Cl-) < 50 ppm
Sulphate ions (SO4) < 50 ppm
Sulphide ion (S) none
Ammonium ions (NH4) none
Silica (SiO2) < 30ppm