EasyManua.ls Logo

AERMEC NXW - INPUTS;OUTPUTS Menu - Alarm & Valve Outputs; Anti-freeze & Compressor Phase Alarms; Evaporator Pump Digital Outputs; Solenoid Valves Digital Outputs

AERMEC NXW
136 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
INPUTS/OUTPUTS menu - Anti-freeze resistance and compressor phases alarm digital outputs
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/exits.
B Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C 07: indicates the status of the digital output linked to the anti-freeze
resistance. The status of this output can be one of the following:
• Closed = normal functioning
• Open = Anti-freeze alarm active;
D 08: indicates the status of the digital output linked to the compressor
phases alarm. The status of this output can be one of the following:
• Closed = compressor phases alarm in progress;
• Open = no alarm in progress;
B
Input/Output
Master digital output
A
C
07= Antifreeze heater:
Close
08= ASerius alarm:
Open
D
INPUTS/OUTPUTS menu - Solenoid valves digital outputs
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/exits.
B Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C/D 10-11: indicates the status of the solenoid valves indicated,
the status of this output can be one of the following:
• Closed = valve ON;
• Open =valve OFF;
• --- = valve not present;
INPUTS/OUTPUTS menu - Evaporator pump digital outputs
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/exits.
B Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C 09: indicates the status of the pump indicated, the status of
this output can be one of the following:
• Closed = pump ON;
• Open = pump OFF;
B
Input/Output
Master digital output
A
C
09= Evaporator pump 1:
Open
B
Input/Output
Master digital output
A
C
10= Liquid solenoid 1:
Close
11= Liquid solenoid 2:
---
D
INPUTS/OUTPUTS menu - 4-way valves digital outputs
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/exits.
B Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C/D 12-13: indicates the status of the 4-way valves indicated, the
status of this output can be one of the following:
• Closed = valve ON;
• Open =valve OFF;
• --- = valve not present;
B
Input/Output
Master digital output
A
C
12= 4Way valve circ.1:
Open
13= 4Way valve circ.2:
---
D

Table of Contents