40
IVES0LJ 1707 - 5880761_01
• Maximum number of MASTER fan coils = 64
• Maximum number of SLAVE fan coils which can be connected to each MASTER = 5
VMF-E5B / VMF-E5N MAIN INTERFACE FOR SYSTEM SUPERVISION
Recessed panel available in two colours,
VMF-E5B white and VMF-E5N black
with backlit graphic LCD display and
capacitive keypad, for centralised
command/control of a complete
hydronic system consisting of:
• Fan coils: up to 64 fan coils zones
composed of 1 master + max 5 slaves.
• Chiller/Heat pump equipped with
Modu_Control, GR3 and pCO2 / PCO
controls (RS 485 interface mandatory
accessor y, MODU -48 5A, AER48 5,
AER485P2 / AER485P1 respectively)
• Circulators: maximum 12 configurable
zone circulators.
• Boiler: boiler consent management for
hot water production.
• Heat recovery units: maximum 3
consents for programmable heat
recovery units according to time periods
and/or through the air quality detection
obtained with VMF-VOC accessory.
• Domestic hot water module: complete
management of domestic hot water
production through the control of:
- Diverter valve/circulator
- Integrative heater
- Accumulation temperature probe
- Anti-Legionella cycle
The main feature is the possibility
of managing the system through
alg orit h m s aim ed at achieving
environmental comfort with a view to
energy saving.
For complete information on operation
refer to the accessory manual.
ATTENTION!: Not all the functions of the accessory can be applied to the unit. Check the compatibility of the functions with the
configuration of the unit and of the other accessories applied. For complete information relating to the functions please refer to the
technical manual of the unit and accessories.
ACCESSORIES
VMF-E1
VMF-SIT
VED
VMF-E1
VMF-SIT
VED
VMF-E1
VMF-SIT
VED
VMF-E5B
VMF-E5N
VMF-E4VMF-E4VMF-E4
ATTENTION: The VMF-E5 panel allows you to manage
individual masters.
The slave units connected to each master cannot be managed
individually by the VMF-E5 panel, but they take on the settings of