EasyManua.ls Logo

aero pure AP904-SL - User Manual

aero pure AP904-SL
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
VENTILATION FAN
MODEL: AP904-SL & AP904H-SL
AP124-SL & AP124H-SL
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, PLEASE READ THE FOLLOWING:
1.Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or
telephone number listed in the warranty. 2. Before servicing or cleaning unit, switch power off at service panel and lock the service
disconnecting means to prevent power from being switching on accidentally. If the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag, to the service panel. 3. Installation work and electrical wiring must be
done by a licensed person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and
standards. 4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning
equipment to prevent backdraft. Follow the heating equipment manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and the local code authorities. 5. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities. 6. Ducted fans must always be vented to the outdoors. 7. Acceptable for use over a tub or
shower when connected to a GFCI (Ground Fault Circuit Interrupter) protected branch circuit (ceiling installation only). 8. This unit
must be grounded. 9. Never place a switch where it can be reached from a tub or shower. 10. Not for use in kitchens. This unit may
be installed in a wall for a non- wet application. 11. Install fan at least 2.5 m (8 feet) above the floor. 12 WARNING: To reduce the risk
of fire or electric shock, do not use this fan with any solid-state speed control device. 13. The fan must not be installed in a ceiling
thermally insulated to a value greater than R40.
CAUTION
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up for wall
application.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall and construction dust off power unit.
4. Please read specification label on product for further information and requirements.
CLEANING & MAINTENANCE
For quiet and efficient operation, long life, and attractive appearance, lower or remove grille and vacuum interior of unit with the
dusting brush attachment.
The motor is permanently lubricated and never needs oiling.
OPERATION
See “Connect Wiring” for details. (AP904/124-SL)
The humidity control and fan and light can be operated separately. Do not use a dimmer switch to operate the humidity control or
light. See “Connect Wiring” for details. (AP904/124H-SL)
Humidity Sensor For AP904/124H-SL
SENSOR OPERATION
The humidity-sensing fan uses a sophisticated humidity sensor that responds to: (a) rapid to moderate (user-adjustable)
increases in humidity or (b) humidity above a user-adjustable set-point (50%-100% relative humidity). The humidity sensor
may occasionally turn the fan ON when environmental conditions change. If the fan continuously responds to changing
environmental conditions, “H” (means “humidity”) adjustment may be required. This figure is factory-set for about 75% RH.
SENSITIVITY ADJUSTMENT
The “H” has been factory set for most shower applications. However, if the fan is in a tub area or is being used for dampness
control, the “H” may need to be increased toward maximum “+”. If the control is responding too often to changing
environmental conditions, movement toward less “-” “H” may be required.
To adjust the “H”:
1. Disconnect power at service entrance.
2. Through the grille, locate the slot marked “H”.
3. Carefully rotate the “H” adjustment toward “+” or “-”.
4. Turn on power and check operation by turning on the shower or other humidity source until the fan turns on.
5. Repeat above steps if necessary.
When the temperature changes, humidity sensor values will have deviation.
TIMER ADJUSTMENT
The humidity sensing fan has a “T” (means timer) that can be adjusted from 5 to 60 minutes (factory-set at about 20 minutes).
This “T” controls the length of time that the fan remains ON after the sensor has stopped sensing a rise in humidity
and the humidity level is below the user-adjustable set-point. To adjust the “T”:
1. Disconnect power at service entrance;
2. Through the grille, locate the slot marked “T”;
3. Carefully rotate the “T” adjustment to desired setting (from 5 to 60 minutes).
4. Check operation by turning on a humidity source until the fan turns on.
5. Turn humidity source off and time the unit.
6. Repeat above steps if necessary.
READ AND SAVE THESE INSTRUCTIONS
Installer: Leave this manual with the homeowner
Question and Answer IconNeed help?

Do you have a question about the aero pure AP904-SL and is the answer not in the manual?

Summary

WARNING

CAUTION

CLEANING & MAINTENANCE

OPERATION

SENSOR OPERATION

Explains how the humidity sensor works and user-adjustable set-points.

SENSITIVITY ADJUSTMENT

Details how to adjust the humidity sensor sensitivity for optimal performance.

TIMER ADJUSTMENT

Guides on adjusting the fan's run time after humidity levels drop below set-point.

PLAN THE INSTALLATION

ASSEMBLY INSTRUCTIONS

INSTALL DUCTWORK

Instructions for connecting ductwork to the fan housing for proper ventilation.

CONNECT ELECTRICAL WIRING

Guides on connecting the fan's electrical wiring to the house power supply.

INSTALL GRILLE

Steps for attaching the grille assembly to the fan housing after installation.

SERVICE PARTS

WARRANTY

Overview

This document provides comprehensive instructions for the installation, operation, and maintenance of a ventilation fan, specifically models AP904-SL, AP904H-SL, AP124-SL, and AP124H-SL. It emphasizes safety precautions, proper installation techniques, and features related to humidity sensing and timer functions.

The primary function of this device is general ventilation, designed to exhaust air from indoor spaces to the outdoors. It is explicitly stated that the fan should not be used in cooking areas or to exhaust hazardous or explosive materials and vapors. The fan is suitable for ceiling installation, accommodating pitches up to 12/12 (45 degrees), and can also be installed in a wall for non-wet applications. A key safety feature is its suitability for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) protected branch circuit, but only for ceiling installations. The unit must be grounded, and switches should not be placed where they can be reached from a tub or shower. Furthermore, the fan must be installed at least 2.5 meters (8 feet) above the floor and should not be used with any solid-state speed control device. It is also important that the fan is not installed in a ceiling thermally insulated to a value greater than R40.

Installation involves several critical steps. First, the installer needs to identify the appropriate hanger bar length (short or long) based on the distance between framing members. The hanger bars are designed to fit between joists, and the housing is secured to the joist using screws. The manual illustrates two methods for mounting: with mounting holes and a hanger bar, or with hanger bars only. It also provides specific instructions for mounting to I-joists. Proper ductwork connection is crucial for optimal performance. The manual recommends using insulated flexible duct for the quietest operation and advises keeping duct runs short and straight. All ductwork connections must be secured with duct tape to ensure airtightness. The importance of insulation around ducts to reduce energy loss and inhibit mold growth is also highlighted. Electrical wiring involves connecting the unit to a 120V AC power supply using UL-approved connectors, with detailed wiring diagrams provided for both the standard (AP904/124-SL) and humidity-sensing (AP904/124H-SL) models. After installation, the grille assembly is attached by pinching its springs and positioning it into the housing until it secures to the ceiling.

Usage features vary slightly between the standard and humidity-sensing models. For the AP904/124-SL, the humidity control, fan, and light can be operated separately. However, a dimmer switch should not be used for either the humidity control or the light. The AP904/124H-SL model incorporates a sophisticated humidity sensor. This sensor automatically turns the fan ON in response to rapid or moderate increases in humidity, or when humidity levels exceed a user-adjustable set-point (ranging from 50% to 100% relative humidity). The factory default for humidity sensitivity ("H") is set at approximately 75% RH, which is suitable for most shower applications. Users can adjust this sensitivity if the fan responds too often to changing environmental conditions or if it's used in a tub area or for general dampness control. Adjustment involves disconnecting power, locating the "H" slot on the grille, and rotating it towards "+" for increased sensitivity or "-" for decreased sensitivity. The humidity-sensing fan also includes a timer ("T") function, adjustable from 5 to 60 minutes (factory-set at about 20 minutes). This timer controls how long the fan remains ON after the sensor stops detecting a rise in humidity and the humidity level drops below the set-point. Similar to humidity sensitivity, the timer can be adjusted by disconnecting power, locating the "T" slot, and rotating it to the desired setting.

Maintenance features for this ventilation fan are straightforward and designed for long-term, efficient operation. For cleaning, users are instructed to lower or remove the grille and vacuum the interior of the unit using a dusting brush attachment. This helps maintain quiet and efficient operation, as well as the attractive appearance of the unit. A significant advantage is that the motor is permanently lubricated and never requires oiling, reducing the need for complex maintenance procedures. Users are also advised to keep drywall and construction dust off the power unit to prevent motor bearing damage and noisy or unbalanced impellers. The manual includes a detailed list of service parts, such as the grille assembly, grille springs, humidity sensor, motor plate, motor, blower wheel, wire panel/harness assembly, hanger bar kit, wiring plate, housing, and damper/duct connector, along with smaller components like nuts, washers, screws, and isolators. Instructions for replacing parts, particularly the blower assembly, are provided, emphasizing the need to disconnect power before any replacement work.

The product comes with a limited warranty covering all defects in workmanship or materials for the mechanical and electrical parts for 72 months from the date of purchase. The warranty requires the original sales receipt as proof of purchase and is valid for the original retail purchaser. It covers replacement of defective mechanical or electrical parts under normal household use. However, the warranty explicitly excludes damages from improper installation, shipping, misuse, abuse, accident, alteration, lack of proper care and maintenance, service by unlicensed electricians, and labor or transportation charges for repairs. It also does not cover fluorescent lamp starters and tubes. This limited warranty is provided in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. The warranty states that the provided remedy is exclusive and does not cover incidental or consequential damages, though some state laws may vary regarding these exclusions and limitations.

aero pure AP904-SL Specifications

General IconGeneral
ModelAP904-SL
OscillationNo
TimerNo
Remote ControlNo
Power Consumption11.7 Watts
Power11.7 W

Related product manuals