EC Fan Speed settings selected on installation
(Low & High speed levels are 100% adjustable)
Typical Ventilation Settings at 100 Pa
Rated Voltage
Maximum Air Volume (at 0 Pa)
Air Volume (at 100 Pa)
Thermal Efficiency
Specific Power Input
Power Supply
Maximum Power Input
Maximum Current
Filter Class (conforming to EN779)
Duct Connection Ø
Condensate Discharge Ø
Protection Class
Operating Temperature
Operating Humidity
Dimensions (W x H x D)
Weight
*Low speed air flow is given for 50 Pa.
450 m³/h (125 l/s)
370 m³/h (103 l/s)
90.5%
0.259 W/m³/h
230V / 1PH / 50Hz
169 W
1.5 A
G4 (F7 optional)
160 mm
22 mm
IP44
-10°C to +40°C
0% to 80% RH
710 x 725 x 630 mm
41 kg
50 m³/h
3.0 V
Low
160 m³/h
5.5 V
Medium
310 m³/h
8.0 V
High
370 m³/h
10.0 V
Boost