TUBING CONNECTIONS
11. TUBING CONNECTIONS
When the outdoor unit is installed above the indoor unit, an oil trap is required every 5m along the
suction line at the lowest point of the riser. In case the indoor unit is installed above the outdoor, no
trap is required.