Multi Split DUO DCI
REFRIGERANT
R410A
HEAT PUMP
TM DUODCI-A-1-GB JUNE 2005
Indoor Units Outdoor Units
FLO 9 DC INV
DUO 50 DCI
FLO 12 DC INV
SX 9 DC INV
SX 12 DC INV
BS 12 DC INV
K
9 DC INV
K
12 DC INV
Technical Manual
Question and Answer IconNeed help?

Do you have a question about the Airwell SX 12 DC INV and is the answer not in the manual?

Airwell SX 12 DC INV Specifications

General IconGeneral
Cooling Capacity3.5 kW
SEER6.1
SCOP4.0
Energy Efficiency ClassA++
Noise Level (Outdoor)49 dB

Summary

2. PRODUCT DATA SHEET

2.2.3 K 9 DCI Specifications

Technical specifications for the K 9 DCI indoor unit.

2.2.5 SX 9 DCI Specifications

Technical specifications for the SX 9 DCI indoor unit.

2.2.7 BS 12 DCI Specifications

Technical specifications for the BS 12 DCI indoor unit.

2.2.4 K 12 DCI Specifications

Technical specifications for the K 12 DCI indoor unit.

2.2.6 SX 12 DCI Specifications

Technical specifications for the SX 12 DCI indoor unit.

5. PERFORMANCE DATA

5.1 FLO 9 DCI Performance

Cooling and heating capacity data, and correction factors for FLO 9 DCI.

5.2 FLO 12 DCI Performance

Cooling and heating capacity data, and correction factors for FLO 12 DCI.

5.3 K 9 DCI Performance

Cooling and heating capacity data, and correction factors for K 9 DCI.

8. WIRING DIAGRAMS

9. REFRIGERATION DIAGRAMS

11. CONTROL SYSTEM

11.17.3 Compressor Overheating Protection

Control zones for compressor temperature protection.

11.17.5 Heat Sink Over Heating Protection

Protection against overheating of the heat sink.

11.17.6 Deicing Protection Procedure

Describes the step-by-step procedure for deicing protection.

11.17.7 Condensate Water Overflow Protection

Logic for condensate water overflow detection and handling.

11.25 SW Parameters

Software parameters related to indoor unit fan speed and compressor frequency.

11.25.2 Outdoor Units SW Parameters

Software parameters for outdoor units, including compressor limits and fan speed.

11.17 Protections

Overview of system protections and fault codes.

11.17.4 Compressor Over Current Protection

Protection against over current for the compressor.

11.17.6 Outdoor Coil Deicing Protection

Conditions and procedures for outdoor coil deicing.

11.3 Compressor Frequency Control

Details on NLOAD setting and compressor frequency management.

12. TROUBLESHOOTING

1.1 Dual Split System Failures

Lists common failures in dual split systems and their corrective actions.

1.3.2 Outdoor Unit Diagnosis

Corrective actions for outdoor unit faults identified by MSMP.

1.3.3 MSMP Fault Code for Indoor Unit

MSMP fault codes and troubleshooting for indoor units.

1.3.4 Indoor Unit Diagnosis

Corrective actions for indoor unit faults identified by MSMP.

1.3 MSMP Diagnostics

Information on judging system status using MSMP diagnostics and fault codes.

1.6 Safety Precautions

Important safety warnings regarding high voltage and capacitor discharge.