2-2
PRODUCT DATA SHEET
SM FBFRPM 1-A.0 GB
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2.2 FBF030 / GCN30NRCT
Model Indoor Unit FBF030
Model Outdoor Unit GCN 30NT/30NRCT
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
(1)
Btu/hr 28,500 30,700
kW 8.35 9.00
Power input
(1)
kW 2.92 2.80
EER (Cooling) or COP(Heating)
(1)
W/W 2.86 3.21
Energy efficiency class C C
Power supply V/Ph/Hz 400V/3N/50Hz
Rated current A 3 x 5.6 3 x 5.5
Starting current A 35
Circuit breaker rating A 3 x 16
INDOOR
Fan type & quantity Centrifugal x 3
Fan speeds H/M/L 1320x1220x1140 1320x1220x1140
Air flow
(2)
H/M/L 1240/1145/1070 1240/1145/1070
External static pressure Min-Max N/A N/A
Sound power level
(3)
H/M/L 64/62/60 64/62/60
Sound pressure level
(4)
H/M/L 53/51/49 53/51/49
Moisture removal l/hr 3.2
Condensate drain tube I.D mm 25
Dimensions WxHxD 1285x660x198 1280x660x206
Weight kg 34
Package dimensions WxHxD 1365x744x278 1379x744x310
Packaged weight kg 42
Units per pallet units 6
Stacking height units 3
OUTDOOR
Refrigerant control Capillary tube ( restrictor for heating)
Compressor type, model Rotary
Fan type & quantity Axial & 1
Fan speeds H/L RPM 850
Air flow H/L m3/hr 3150
Sound power level H/L dB(A) 69
Sound pressure level
(4)
H/L dB(A) 59
Dimensions WxHxD mm 900x860x340
Weight kg 78
Package dimensions WxHxD mm 985x907x435
Packaged weight kg 82
Units per pallet units 6
Stacking height units 2
Refrigerant type R410A
Refrigerant chargless distance kg/m 2.45/15
Additional charge per 1 meter g/m 30
Connections between units
Liquid line In.(mm) 3/8"(9.53)
Suction line In.(mm) 5/8"(15.88)
Max .tubing
length
m. Max.50
Max .height
difference
m. Max.25
Operation control type Remote control
Heating elements kW
Others Crankcase heater (50W), 3 Phase Protector

Related product manuals