7-1
ELECTRICAL DATA
SM SX DCI 1-A.3 GB
7. ELECTRICAL DATA
7.1 Single Phase Units
MODEL SX 9 DCI SX 12 DCI SX 18 DCI SX 24 DCI SX 30 DCI
Power Supply
To indoor To indoor To indoor To outdoor To outdoor
1PH-230V-
50Hz
1PH-230V-
50Hz
1PH-230V-
50Hz
1PH-230V-
50Hz
1PH-230V-
50Hz
Max Current, A 10 10 12 14 15
Inrush Current A 35 35 35 45 45
Starting Current A 10.5 10.5 10.5 10.5 10.5
Circuit Breaker A 16 16 20 20 20
Power Supply Wiring No.X Cross
Section mm
2
3 x 1.5 mm
2
3 x 1.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
Interconnecting Cable No.X Cross
Section mm
2
4 x 1.5 mm
2
4 x 1.5 mm
2
4 x 2.5 mm
2
4 x 2.5 mm
2
4 x 2.5 mm
2
NOTE
Power wiring cord should comply with local lows and electrical
regulations requirements.