PERFORMANCE DATA
HKD DCI 17 Version - 2
5. Performance data
5.1 AWSI-HKD009-N11 / AWAU-YKD009-H11
1) Cooling
ID COIL ENTERING AIR DB/WB TEMPERATURE [C
0
]
OD COIL ENTERING AIR DB
TEMPERATURE [C
0
]
DATA
22/15
24/17
27/19
29/21
32/23
-10 - 20
(protection range)
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
PI
25 - 50 % of nominal
25
TC
2.56
2.73
2.90
3.06
3.23
SC
1.98
2.02
2.06
2.10
2.14
PI
0.61
0.62
0.63
0.64
0.66
30
TC
2.44
2.61
2.77
2.94
3.11
SC
1.93
1.97
2.01
2.05
2.09
PI
0.68
0.69
0.70
0.72
0.73
35
TC
2.32
2.48
2.65
2.82
2.98
SC
1.88
1.92
1.96
2.00
2.04
PI
0.75
0.76
0.78
0.79
0.80
40
TC
2.19
2.36
2.53
2.69
2.86
SC
1.83
1.87
1.91
1.95
1.99
PI
0.82
0.83
0.85
0.86
0.87
46
TC
2.04
2.21
2.38
2.55
2.71
SC
1.77
1.81
1.85
1.89
1.93
PI
0.91
0.92
0.93
0.94
0.96
Legend:
TC - Total Cooling Capacity [kW] SC - Sensible Capacity [kW]
PI - Power Input [kW] WB - Wet Bulb Temperature
DB - Dry Bulb Temperature ID - Indoor
OD - Outdoor