Engineering manual
324
3 Outdoor units troubleshooting
Outdoor unit - Compressor discharge temperature protection
Remote controller display d1, d8
Possible reason
Discharge temperature abnormal
Discharge temperature sensor abnormal
Outdoor electrical board abnormal liquid solenoid valve abnormal
Diagnostic
Yes
No
Yes
No
No
No
Is liquid solenoid valve
connectin
h than 107℃?
Connect well the wires, reset
power supply and run the
unit again
Check refrigerant quantity
Change a new discharge
temperature sensor
Change outdoor electrical
board