Service Manual
Flow Logic III

Questions and Answers

  • G
    Gary HayesAug 19, 2025
    What to do if my Airwell Air Conditioner shows a cooling/heating lack of refrigerant alarm?
    • A
      Ashley SmithAug 20, 2025
      If your Airwell Air Conditioner is showing a cooling or heating alarm due to a lack of refrigerant, you should check the unit for refrigerant leakage and verify the readings from the high and low pressure sensors are accurate.
  • M
    murphyjeromeAug 22, 2025
    How to fix EEPROM failure in Airwell AWAU-YDV280-H13 Air Conditioner?
    • K
      Katherine DavisAug 22, 2025
      In case of EEPROM failure in your Airwell Air Conditioner, turn both BM1_1 and M1_2 to the "OFF" position, then re-energize the unit to see if the error clears.
  • K
    Katie MasonAug 25, 2025
    What to do if Airwell Air Conditioner four-way valve reversing failure?
    • A
      Ashlee CookAug 25, 2025
      If your Airwell Air Conditioner's four-way valve is failing to reverse, have it replaced by after-sales service on site and ensure there is enough refrigerant.
  • D
    David BaxterAug 26, 2025
    How to fix communication failure between indoor and outdoor unit of Airwell Air Conditioner?
    • C
      cklineAug 26, 2025
      If your Airwell Air Conditioner has communication issues between the indoor and outdoor units, have it replaced correctly by after- sales personnel on site.
  • R
    Richard SimpsonAug 28, 2025
    What to do if low pressure sensor disconnection failure in Airwell AWAU-YDV280-H13 Air Conditioner?
    • T
      Thomas HawkinsAug 28, 2025
      If your Airwell Air Conditioner is showing a low pressure sensor disconnection failure, have it replaced correctly by after- sales personnel on site.
  • A
    abrownAug 29, 2025
    What to do if high pressure sensor disconnection failure in Airwell Air Conditioner?
    • B
      brent44Aug 30, 2025
      If your Airwell Air Conditioner is showing a high pressure sensor disconnection failure, have it replaced correctly by after- sales personnel on site.
  • T
    timothy27Aug 31, 2025
    What to do if high pressure switch disconnection failure in Airwell AWAU-YDV280-H13?
    • L
      Lawrence TapiaAug 31, 2025
      If your Airwell Air Conditioner is showing a high pressure switch disconnection failure, have it replaced correctly by after- sales personnel on site.
  • R
    robert68Sep 2, 2025
    What to do if the unit compression ratio is too low in Airwell AWAU-YDV280-H13?
    • S
      Shane Grant MDSep 3, 2025
      If your Airwell Air Conditioner indicates the unit compression ratio is too low, have it replaced correctly by after- sales personnel on site and ensure there is enough refrigerant.
  • H
    hhigginsSep 5, 2025
    How to fix communications between outdoor units failure in Airwell Air Conditioner?
    • M
      Michael ScottSep 5, 2025
      If your Airwell Air Conditioner is experiencing communications failure between outdoor units, have it replaced correctly by after- sales personnel on site.
  • R
    Robin WilliamsSep 7, 2025
    What to do if fan motor 1 or 2 overcurrent in Airwell Air Conditioner?
    • U
      ujohnsonSep 7, 2025
      If your Airwell Air Conditioner's fan motor 1 (left fan) or fan motor 2 (right fan) is showing an overcurrent, have it replaced correctly by after-sales personnel on site.

Summary

Specification

Piping diagram

Specific Model Piping Diagrams

Schematic diagrams illustrating piping connections for various outdoor unit models.

Wiring diagram

Capacity calculation due to capacity modification coefficient

Operation range

Installation

9.1 Safety

Crucial safety instructions and warnings to be followed before and during installation.

9.5 Construction of refrigerant pipe

Procedures for determining pipe specifications and restrictions for refrigerant piping.

Trial operation

12.3 Trial operation confirmation

Step-by-step confirmation for trial operation, focusing on wired controller status.

Outdoor control board photo

Outdoor PCB dip switch setting

BM1 Definition

Details functions and settings for BM1 DIP switches related to unit operation.

BM2 Definition

Details functions and settings for BM2 DIP switches, including quiet running and anti-snow.

BM3 Definition

Defines BM3 DIP switch functions for unit type and HP setting.

BM4 Definition

Details BM4 DIP switch functions for quantity lock, drop selection, and protocol.

Outdoor system control function

15.1 Start Control

Explains conditions and procedures for compressor start and protection control.

15.2 Target pressure control

Details target pressure settings for cooling/heating and their impact on compressor frequency.

15.4 Pressure protection control

Explains high and low-pressure protection mechanisms to prevent system damage.

15.5 Overheating protection control

Details protection measures for compressor overheating based on temperature readings.

15.6 Current protection control

Describes how the system manages compressor operating frequency based on current limits.

Failure code

Master unit digital tube display failure code

Lists failure codes displayed on the master unit, their definitions, and descriptions.

Indoor unit LED status

Information on LED status indicators for indoor units and their corresponding failure codes.

Troubleshooting

2. Abnormity detection method

Steps to detect abnormalities, focusing on sensor checks and connections.

3. Abnormity confirmation conditions

Criteria used to confirm an abnormality, based on AD values and operating conditions.

4. Possible causes

Lists potential causes for detected abnormalities, such as sensor issues or connection problems.

APPENDIX Sensor Resistance Table