19
EN
Activation delay. This allows you to select a delay time for switching on the production unit,
congurable in minutes, from 0 to 7 (by default, 3 min.).
DHW function. (Only available in installations with AZX6GAW[XXX] gateway) This allows
you to activate or deactivate (On/Off) the domestic hot water (DHW) function in the systems
connected to the CCP. Function activated by default.
Cooling mixing valve. (Only available in installations with AZX6GAW[XXX] gateway) This
allows you to congure the operation of your installation depending on whether or not you
have a cooling mixing valve.
Select Manual in the case of having cooling mixing valves in your installation, in which case
they must be set at 18 °C. If the installation does not have a cooling mixing valve, select Auto
so that the installation works automatically with the temperature read by the system. By
default, it is set to Manual.
LWT temperatures. (Only available in installations with AZX6GAW[XXX] gateway, provided
that the air to water unit is not congured to work automatically, allowing the imposition
of working temperatures) This allows you to dene the LWT temperatures of the air to
water unit for cooling and heating modes. The temperature range is dened by the AC unit.
Default values:
- Air in cooling mode: 10 ºC
- Radiant in cooling mode: 18 °C
- Air in heating mode: 50 °C
- Radiant in heating mode: 35 °C
Mode Demand
Control relays
O1 O2 O3 O4 O5 O6
Stop Off - - - -
- -
Cooling
Air ON - ON - - -
Radiant ON - - ON - -
Off ON - - - - -
Heating
Air - ON - - ON -
Radiant - ON - - - ON
Off - ON - - - -
Dry
On ON - - - - -
Off ON - - - - -
Ventilation
On - - - - - -
Off - - - -
- -