The Set point energy saving parameter defines what the set point will be when this mode is active and the
Energy saving duration parameter defines the duration of this mode in hours. It never activates if it is
configured at 0.
This mode may optionally be activated and deactivated whenever you want using the external button connected to one
of the digital inputs, and to do so the corresponding input should be configured as "Remote energy saving”.
COMPRESSOR PROTECTION DELAY (according to model)
This protects the compressor, preventing continuous stops and start-ups in certain exceptional cases.
The Comrpessor Protection parameter allows choosing between 2 types of delay:
OFF-ON: Minimum time the compressor should stay stopped before each start-up.
ON: Delay time as from when the compressor should activate until it does activate.
The Protection delay time parameter defines the time of the previous parameter.
FUNCIONAMIENTO EN CASO DE FALLO EN SONDA 1
If probe 1 fails (failure, disconnection, etc. ), the compressor/solenoid* operates according to the times
programmed in the following parameters:
Compresor ON error s1: Compressor/solenoid* time in operation in the event of fault in probe 1.
Compresor OFF error s1: Compressor/solenoid* time stopped in the event of fault in probe 1.
SET POINT LOCKINGS
Using the Set Point upper limit and Set Point lower limit parameters, it is possible to set a top and bottom limit for
the Set point (SP) parameter, which prevents being able to set a set point that is too low or too high that might
damage the installation or the stored product.
STOP COMPRESSOR WHEN THE DOOR IS OPENED
This defines if the compressor/solenoid* will be stopped whenever the cold room's door is opened. To do so, one of
the digital inputs should be configured as "door contact" (See page 25).
If the door stays open longer than the value programmed in the Inact. with door open parameter, the
compressor/solenoid* will return to normal operation (See page 25).