Drip time after defrost
This is establishing using the Drip time parameter of the H menu and defines the time added at the end of the defrost
to allow removing any water left in the evaporator.
During this time, the compressor/solenoid* and fans will be stopped (except if the defrost is by air).
Message displayed during defrost
This is established using the Defrost message parameter, and you can choose between displaying the real
temperature captured by probe 1, show the temperature capture by probe 1 at the start of the defrost, or display the
DEFROST message.
The Message duration parameter defines how long this message is displayed, after the drip time and start up delay of
the fans (See page 19).
Other parameters
Using the Defrost at Start-up parameter, you can configure if the unit carries out or not a defrost when it receives
power (first start up or after a fault in the power supply).
If the "YES" option is chosen, defrost starts after the time defined in the Defrost delay at Start-up parameter on the
H menu.
Remote defrost
This function allows activating the defrost of the unit using an external button, connecting it to one of the digital inputs
that must be configured as "remote defrost”.
*In the panels AKO-15658 / 15659, the liquid solenoid is controlled instead of the compressor.