EasyManua.ls Logo

aldes EasyVEC - Page 23

aldes EasyVEC
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
EN
Symptom 1 Symptom 2 Verifications Action
A fault is displayed on the remote
control
- See error code table below
The fan unit will not start
The remote control screen
(depending on version) is
switched on
- Check all wiring
- Check the motor: must be supplied directly with 230V~. Activate the motor run
control
Replace the faulty part: Control PCB
or motor
The remote control screen
(depending on version) is
switched off
- Check all wiring.
- Check fuse on Control PCB
Replace the fault part: remote
control or Control PCB.
Version without remote
control
- Check all wiring
- Check capacitor (depending on version)
- Check speed controller fuse
- Check voltage at the output of the speed controller (depending on version)
- Check the motor: 230V AC direct supply. In addition, for EC motors (EasyVEC
®
Compact 2000): activate the motor run control
Replace the faulty part: fuse,
capacitor, speed controller or motor
The fan unit starts and then stops - Check all wiring.
The fan does not run at the
selected set-point
Low speed
"Check that the impeller is not rubbing against the casing
- Check the capacitor (depending on version).
- Adjust the speed controller (depending on version).
- Check the output voltage from the speed controller or Control PCB (depending
on version).
- Check the functioning of the pressure sensor(s) (depending on version,
simulating a slight over or under pressure in the pressure tubes.
- Check the motor: Directly from 230V AC supply In addition, for EC motors
(EasyVEC
®
Compact 2000 & micro-watt/micro-watt + versions): activate the
motor run control (contact Technical Support)"
Replace the faulty part: capacitor,
additional pressure sensor (micro-
watt + version), speed controller,
electronic control PCB or motor
High speed
- Check the fire mode thermo-trip device and wiring (depending on version)
- Check the condition, position and connectivity of pressure tubes (depending on
version), unblock if necessary.
- Check the above points (low speed).
Replace the faulty part: thermo-trip
device (triggering fire mode). See
above (low speed)
The speed does not change
when the set point is
changed
- Inspect the aeraulic network looking for leaks.
- Check the above points (high speed - low speed)
- See A45 above (high speed - low
speed)
The fan rotates in the wrong
direction
- Check the wiring in the motor terminal unit (EasyVEC® 1000 to 2500)
The micro-watt+ and constant
flow rate modes are no longer
available (micro-watt+ version)
- Check the wiring on the additional pressure sensor (micro-watt+ version)
Change the additional pressure
sensor (micro-watt+ version)
Meaning Diagnostics/Solutions
E.50 Motor speed return = 0 rpm Motor disconnected or fan stuck or motor U/S
E.51 Motor speed return < 100 rpm Fan is rubbing or motor is U/S
E.52
Fan does not reach minimum pressure set point
Check full system (network load and loss through leakage)
Check the state and connectivity of capillaries, unblock if necessary.
Constant pressure: 80 Pa.
Self-balanced regulated pressure: 50 Pa
Humidity-controlled regulated pressure: 80 Pa
T-Flow regulated pressure: 110 Pa
Expert regulated pressure: 50 Pa
Constant airflow: NA
Control 0-10 V: NA
E.53 Incoherent pressure reading (too high) Pressure sensor U/S
E.88 Communications fault involving remote control Remote control U/S
E.251 Operating in Fire Mode, thermo-contact circuit open Thermocontact circuit or thermocontact U/S
All these error numbers disappear when the fault is resolved and reset (See 6.4).
In the event of a problem, you may carry out a total system reset (Reset: See 6.4) and if the problem persists, contact our After
Sales Service Dept.).

Related product manuals