17
Filtaire
In areas where LPG quality is poor it may be necessary to install
FILTAIRE or FILT-EZE Gas trap at the outlet of your vaporizer.
For model Z150 use FILTAIRE model F4 P/N 20536-ASME.
For model Z100 above 14ºF (-10ºC) ambient temperature (35
psig (2.4 bar) saturation pressure) use FILT-EZE P/N 82288.
Below 14ºF (-10ºC), use FILTAIRE model F4 P/N 20536-ASME.
For models Z25, Z40 and Z50 use FILT-EZE P/N 82288.
Installing Multiple Vaporizers
Multiple ZIMMER vaporizers can be manifolded together to
increase the total system capacity.
Manifold the inlets and outlets together using similar length
piping runs. It is best to keep the piping as short as possible.
Install an isolation valve at the inlet and outlet of each vaporizer.
Install an appropriately sized regulator with Fluorocarbon
elastomer (Viton) seat after the outlets have been manifolded
together. For more than two vaporizers use one adequately
sized regulator with a Fluorocarbon elastomer (Viton) seat.
Common piping problems
Problem: Frost or condensation on the liquid LPG piping.
Cause: Vaporizer installed with undersized piping from
storage container to vaporizer.
Reason: Liquid LPG boils in the pipe before the vaporizer
causing a reduction in vaporization capacity.
Problem: Moisture or water droplets on the piping before the
regulator. Frosting of the regulator.
Cause: Outlet regulator installed too far from vaporizer or
below vaporizer outlet.
Reason: High pressure LPG vapor condenses between the
vaporizer outlet and the regulator.
Problem: Downstream component failure.
Cause: Drip leg or filter is not installed or is too small.
Reason: Oils or heavy ends collect in downstream regulators
and other components.