22
Shutting down the system
For overnight or short time periods:
Because the ZIMMER uses only a small amount of electricity
(e.g. approximately 300 - 600 watts in 1 PH operation for Z50)
when there is no load, it is suitable to leave the power engaged
even during periods of non-use. If desired, close the vaporizer
outlet isolation valve when the vaporizer is not being used.
For extended periods:
Close the vaporizer outlet isolation valve.
Open the disconnect switch to power off the vaporizer.
Close the inlet valve or tank valve(s) only after the vaporizer has
expanded the remaining gas and pushed it back toward the tank
(approximately 5 minutes). Trapped liquid can expand when
heated causing damage or possible rupture to pipes and
components. Always install hydrostatic relief valves between
isolation valves.