Appendix 8
ELECTRICAL SPECIFICATIONS
Single phase wiring
Z25 (25 kg/hr nominal)***
Voltage L1 to Neutral [V]
100
120
208
220
240
277
Power [kW] *
2.2
2.2
3.0
3.0
3.0
3.0
Current at rated capacity [A] *
22.3
18.6
14.3
13.5
12.4
10.7
Breaker - D/J type [A] (125%) *
30
25
20
20
15
15
Z40 (40kg/hr nominal)***
Voltage L1 to Neutral [V]
100
120
208
220
240
277
Power [kW] *
3.6
3.6
4.8
4.8
4.8
4.8
Current at rated capacity [A] *
35.7
29.8
22.9
21.6
19.8
17.2
Breaker - D/J type [A] (125%) *
45
40
30
30
25
25
Z50 (50 kg/hr nominal)***
Voltage L1 to Neutral [V]
100
120
208
220
240
277
Power [kW] *
4.5
4.5
6.0
6.0
6.0
6.0
Current at rated capacity [A] *
44.6
37.2
28.6
27.0
24.8
21.5
Breaker - D/J type [A] (125%) *
60
50
40
35
35
30
Z100 (100 kg/hr nominal)**/***
Voltage L1, L2 or L3 to Neutral [V]
100
120
208
220
240
277
Power [kW] *
8.9
8.9
11.9
11.9
11.9
11.9
Current at rated capacity [A] *
29.8
24.8
22.9
21.6
19.8
17.2
Breaker - D/J type [A] (125%) *
40
35
30
30
25
25
Z150 (150 kg/hr nominal)**/***
Voltage L1, L2 or L3 to Neutral [V]
100
120
208
220
240
277
Power [kW] *
13.4
13.4
17.9
17.9
17.9
17.9
Current at rated capacity [A] *
44.6
37.2
28.6
27.0
24.8
21.5
Breaker - D/J type [A] (125%) *
60
50
40
35
35
30
Three phase wiring
Z100 (100 kg/hr nominal)***
4-Wire Wye Configuration (4 pole
breaker)
3-Phase Delta Configuration (3 pole
breaker)
Three Phase Line to Line voltage [V]
173
208
360
380
415
480
100
120
208
220
240
277
Voltage L1, L2 or L3 to Neutral [V]
100
120
208
220
240
277
100
120
208
220
240
277
Power [kW] *
8.9
8.9
11.9
11.9
11.9
11.9
8.9
8.9
11.9
11.9
11.9
11.9
Current at rated capacity [A] *
29.8
24.8
22.9
21.6
19.8
17.2
51.5
42.9
39.6
37.5
34.4
29.8
Breaker - D/J type [A] (125%) *
40
35
30
30
25
25
65
55
50
50
45
40
Z150 (150 kg/hr nominal)***
Three Phase Line to Line voltage [V]
173
208
360
380
415
480
100
120
208
220
240
277
Voltage L1, L2 or L3 to Neutral [V]
100
120
208
220
240
277
100
120
208
220
240
277
Power [kW] *
13.4
13.4
17.9
17.9
17.9
17.9
13.4
13.4
17.9
17.9
17.9
17.9
Current at rated capacity [A] *
44.6
37.2
28.6
27.0
24.8
21.5
77.3
64.4
49.5
46.8
42.9
37.2
Breaker - D/J type [A] (125%) *
60
50
40
35
35
30
100
85
65
60
55
50
*Your exact conditions may result in differing power and current.
**Requires three (3) single phase breakers, one for each leg (L1, L2, L3)
***25% capacity derate with 100-120V line to line voltage